Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T22CM03758
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/14/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. The Plan Reviewer tried to contact Registrant of record to discuss plan. The phone number shown on the plans is not in service. The #8 equipment ground conductor shown in the line diagram feeders to panels ‘A’ and ‘B’ are undersized for 2oo amp rated OCPD’s, should be minimum #6 Cu or #4 Al. NEC 250.122. Because the service is being re-worked, verify that the service secondary feeders are sized properly for the total load. What is the total amp rating and voltage, phase, AIC rating of the service? Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/14/2022 | VVERA1 | OUT TO CUSTOMER | Completed |