Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T22CM03757
Parcel: 127042770

Address:
4949 E 5TH ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM03757
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/23/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
06/30/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

The Panel schedules do not correlate with the branch circuits shown on the electrical and lighting plans. The panel directory must accurately specify the loads served. Also the lighting with the encircled R, does that mean Remove or Relocate, or Recessed? In all cases specify the power source for the lighting and devices. NEC 408.4

The current adopted IECC is 2018 not 2012. Please revise the lighting calculation.

If there is no load increase, please specify this on the power and lighting plans.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.