Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T22CM03757
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/24/2022 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
05/24/2022 | JPEELDA1 | FIRE | REVIEW | Approved | |
05/31/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide specifications for all proposed plumbing fixtures. The fixtures shall be listed by a third-party certification agency as complying with the relevant standards. Reference: Section 303.4, IPC 2018. 2. The replacement faucets for the lavatories shall be metering faucets. The metering faucets shall dispense a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds for accessibility. Reference: Section 412.11, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. |
05/31/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
05/31/2022 | ROBERT SHERRY | WATER | REVIEW | Completed | |
06/08/2022 | WBERGER1 | ZONING | REVIEW | Approved | |
06/08/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. 1. Assign branch circuits and panel to all new and relocated luminaires and receptacles that also correlates with complete panel schedules. Ref 2018 IBC sec 107.2.1, 2017 NEC 408.4. |
06/08/2022 | WBERGER1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
06/21/2022 | SSHIELD1 | ENGINEERING | REVIEW | Passed |