09/26/2022 DBENOIT1 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM03715


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Approved/Subject to field approval


ELECTRICAL REVIEW COMMENTS
Conditionally Approved
E4.1 Existing SES Modifications:
Disconnect for Transformer T1 needs to be 200A to match CB rating in Panel A2.


PLUMBING REVIEW COMMENTS:
Denied
Third Plumbing Review:
1). Same- Donor sink water piping still not protected, needs to connect before backflow preventers same as the restrooms & drinking fountain are currently shown - OR if this sink is part the grow process add signage above - IPC 608.9.1 ( if signage is chosen update P1 & P2 sink detail)
2 thru 4 OK
5). OK
6). OK
7). OK
8). OK - Field verify Planter table drain P-traps
9). OK - Self Contained eye wash station
10) OK


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov