Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T22CM03715
Parcel: 132166160

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM03715
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/22/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM03715

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Approved/Subject to field approval


ELECTRICAL REVIEW COMMENTS
Conditionally Approved
E4.1 Existing SES Modifications:
Disconnect for Transformer T1 needs to be 200A to match CB rating in Panel A2.


PLUMBING REVIEW COMMENTS:
Denied
Second Review:
1). Same- Donor sink water piping still not protected, needs to connect before backflow preventers same as the restrooms & drinking fountain are currently shown - OR if this sink is part the grow process add signage above sink same as hose bibs - IPC 608.9.1 ( if signage is chosen update P1 & P2 sink detail)
2 thru 4 OK
5). Newly added plumbing fixture schedule on plan page P2 is missing manufacturer names & model numbers-IPC 303
6). OK
7). OK
8). OK - Field verify Planter table drain P-traps
9). OK - Self Contained eye wash station
10). Lavatories need ASSE 1070 mixing valves -IPC 419.5


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
08/29/2022 STEVE SHIELDS ZONING REVIEW Approved
08/31/2022 ROBERT SHERRY WATER REVIEW Completed
09/08/2022 JPEELDA1 FIRE REVIEW Approved