Permit Number: T22CM03671
Parcel: 12616236A

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM03671
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/16/2022 WBERGER1 ZONING REVIEW Passed
05/16/2022 WBERGER1 ENGINEERING REVIEW Passed
05/16/2022 WBERGER1 NPPO REVIEW Passed
06/08/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T22CM03671
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide an updated complete plan set with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet Zoning and other departmental requirements, conditions and concerns before permit approval.

PLUMBING PLANS:

1. Show an accessible water supply shut off for the dwelling unit, P2903.9.1.
2. Show horizontal branch drainpipes sized with acceptable number of fixture units, Table P3005.4.1. (max 6 units on 2” pipe size). Show a 3” drain between the second clothes washer connection and bathroom.

MECHANICAL PLANS:

1. Show any HVAC alterations, R303.9.

ELECTRICAL PLANS:

1. Smoke alarms are required outside each separate sleeping area, R314.3.2. Show a smoke alarm in each bedroom and outside in the immediate vicinity.
2. Panelboards and overcurrent protection devices shall not be in clothes closets, in bathrooms, or over the steps of a stairway, E3405.5. Relocate the 125A sub-panel.
3. Show the circuit numbers on the plan consistent with the sub-panel schedule labeling, E3602.1 & E3706.2.

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review