Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T22CM03665
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/25/2022 | JPEELDA1 | FIRE | REVIEW | Reqs Change | Plans shall show if you have a fire alarm system If a fire alarm system is installed please add note that the fire alarm modifications require a permit from TFD Plans show exterior work. Add address information to package that confirms that you meet the TFD address requirements (can be obtained from our website under amendments) Questions: Jennifer Peel-Davis Jennifer.Peel-Davis@tucsonaz.gov 520-837-7033 Fire Plans Examiner |
| 05/31/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T22CM03665/BLDG #3, T22CM03664/BLDG #2, T22CM03663/BLDG #1 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Approved BUILDING REVIEW COMMENTS: Denied Sheet G000 – Project team does not include Plumbing engineer while P101 and P201 are provided. Provide plumbing engineer in project team, and clarify scope of work. Sheet G000 – Provide project description which is missing from cover sheet. Sheet G000 – Provide demolition plans to clarify scope of work. Sheet G000 – Civil engineer is in project team while there are no Civil drawings in sheet index. Clarify scope. Sheet G003 – Provide fire alarm information. Is it provided per NFPA 72? Sheet G003 – Provide locations of fire extinguisher cabinets. Sheet G003 – fire resistance rating for exterior walls stating, “EXISTING EXTERIOR BEARING WALLS APPEAR TO BE ORIGINALLY CONSTRUCTED AS 1 HOUR WALLS:” How does this transition to new parapet wall? Is the parapet all fire rated? What is the fire rating of existing roof? Provide justification for non-rated new parapet walls. Sheet G003 – Provide fire rating of existing corridor and corridor doors. Are they one hour rated corridor walls with 60 min. rated door assembly? Sheet G101 – Note 1 states “REFER TO CIVIL AND LANDSCAPE PLANS FOR MORE INFORMATION ON SITE WORK” while no Civil nor Landscape drawings were provided. Clarify scope of work in cover sheet. Is there separate permit? Sheet S0.1 – Special inspections note “CONCRETE” and “STRUCTURAL MASONRY” special inspections required. Where are these in floor plans? Clarify scope of work. Sheet A101 – Keynotes 2.01 states Asbestos Containing Material found while does not state it’ll be removed or encapsulated. Specify course of action – which is it? What is the scope of work of community room? Sheet A104 – Missing key notes. Identify all scope components. Does it provide overflow scupper drain per 2018 IBC 1502.2 secondary drains (emergency overflow)? Sheet A110 – Keynote 8.05 states existing hallway is a “FIRE DOOR” while doesn’t not specify the fire rating. What is the fire rating of existing hallway doors? Sheet A110 – Keynotes 2.01 states Asbestos Containing Material found while does not state that it’ll be removed or encapsulated. Specify course of action – which is it? Sheet A110 – No finish schedule provided? Sheet A201 and A202 – Keynote 2.17 states to “REMOVE EXISTING EXTERIOR CLADDING” while code analysis states that this is fire rated wall. Provide new fire rated stucco exterior wall to show how fire protection integrity is maintained. Sheet A301 – Provide new TPO roofing details at parapet edge and penetrations. Is if fire rated? Class A roofing? (Specify fire resistance) Sheet A501 – Secondary drains (emergency overflow) per 2018 IBC 1502.2 missing. Sheet A501 – Exterior wall and parapet details do not indicate any fire rating. Sheet A601 – Provide code analysis of exterior openings per 2018 Table 705.8 No sprinklered exterior wall. What is the actual allowable area? Less than 10%? Window details do show existing fire ratings per code analysis (Sheet G003). MECHANICAL REVIEW COMMENTS: Conditionally Approved Approved/Subject to field approval ELECTRICAL REVIEW COMMENTS Conditionally Approved E101 ELECTRICAL SITE PLAN: Poor alignment of Keyed Notes. E110 ELECTRICAL - ENLARGED UNIT PLANS: Missing Keynote #7. PLUMBING REVIEW COMMENTS: Denied First Plumbing review: 1). add a demo plan detail to plan page P101 that correlates with new work detail #3 for the 93 NON ADA units. -IPC 106.3.1 2). Roof plan A104 Keynotes are blank, add the note info that correlates with numbers on the roof plan. -IPC 106.3.1 3). Add scupper & downspout sizing calculations to plan page A501.- IPC 1106.3 1106.5 ( detail #3 states Parapets are new) 4). Add secondary scupper detail to plan A501- IPC 1108 If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
| 06/07/2022 | WBERGER1 | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: Wyatt Berger Planner PROJECT: T22CM03665 4131 N Western Winds Dr Building interior remodel (1st Review) TRANSMITTAL DATE: June 7, 2022 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1. Zoning has reviewed the building plans for compliance with DP22-0144. Although it appears that the building plans match the DP, Zoning cannot approve the building plan until the DP is approved. If you have any questions about this transmittal, please contact Wyatt Berger at Wyatt.Berger@tucsonaz.gov. |
| 06/07/2022 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 06/07/2022 | WBERGER1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 06/21/2022 | SSHIELD1 | ENGINEERING | REVIEW | Reqs Change | See Zoning comments |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/21/2022 | VVERA1 | OUT TO CUSTOMER | Completed |