Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM03664
Parcel: 10512024B

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM03664
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/07/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM03663/BLDG #1, T22CM03664/BLDG #2, T22CM03665/BLDG #3

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Approved

MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Approved/Subject to field approval


ELECTRICAL REVIEW COMMENTS
Conditionally Approved
E101 ELECTRICAL SITE PLAN: Poor alignment of Keyed Notes.
E110 ELECTRICAL - ENLARGED UNIT PLANS: Missing Keynote #7.

PLUMBING REVIEW COMMENTS:
Denied
Second Review:
1). OK
2). OK
3). OK
4). Now that the secondary overflow scupper info has been added to plan page A104 & on A501 Detail #3 , the overflow can't
share the same inlet as the primary scupper, must have separate inlets. if the primary scupper inlet became blocked the storm water could not reach the secondary overflow with this current design. -IPC 1108.1


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
07/19/2022 SSHIELD1 ENGINEERING REVIEW Reqs Change See Zoning comments
07/19/2022 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review Section

PROJECT: T22CM03663, T22CM03664, & T22CM03665
4131 N Western Winds Dr
Building interior remodel (2nd Review)

TRANSMITTAL DATE: July 19, 2022

This comment was not addressed. COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. Zoning has reviewed the building plans for compliance with DP22-0144. Although it appears that the building plans match the DP, Zoning cannot approve the building plan until the DP is approved.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
07/19/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/15/2022 JPEELDA1 FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/15/2022 VVERA1 OUT TO CUSTOMER Completed