Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T22CM03663
Parcel: 10512024B

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM03663
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/25/2022 JPEELDA1 FIRE REVIEW Reqs Change Plans shall show if you have a fire alarm system
If a fire alarm system is installed please add note that the fire alarm modifications require a permit from TFD
Plans show exterior work. Add address information to package that confirms that you meet the TFD address requirements (can be obtained from our website under amendments)

Questions:
Jennifer Peel-Davis
Jennifer.Peel-Davis@tucsonaz.gov
520-837-7033
Fire Plans Examiner
05/31/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM03663/BLDG #1, T22CM03664/BLDG #2, T22CM03665/BLDG #3


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Denied
Sheet G000 – Project team does not include Plumbing engineer while P101 and P201 are provided. Provide plumbing engineer in project team, and clarify scope of work.
Sheet G000 – Provide project description which is missing from cover sheet.
Sheet G000 – Provide demolition plans to clarify scope of work.
Sheet G000 – Civil engineer is in project team while there are no Civil drawings in sheet index. Clarify scope.
Sheet G003 – Provide fire alarm information. Is it provided per NFPA 72?
Sheet G003 – Provide locations of fire extinguisher cabinets.
Sheet G003 – fire resistance rating for exterior walls stating, “EXISTING EXTERIOR BEARING WALLS APPEAR TO BE ORIGINALLY CONSTRUCTED AS 1 HOUR WALLS:” How does this transition to new parapet wall? Is the parapet all fire rated? What is the fire rating of existing roof? Provide justification for non-rated new parapet walls.
Sheet G003 – Provide fire rating of existing corridor and corridor doors. Are they one hour rated corridor walls with 60 min. rated door assembly?
Sheet G101 – Note 1 states “REFER TO CIVIL AND LANDSCAPE PLANS FOR MORE INFORMATION ON SITE WORK” while no Civil nor Landscape drawings were provided. Clarify scope of work in cover sheet. Is there separate permit?
Sheet S0.1 – Special inspections note “CONCRETE” and “STRUCTURAL MASONRY” special inspections required. Where are these in floor plans? Clarify scope of work.
Sheet A101 – Keynotes 2.01 states Asbestos Containing Material found while does not state it’ll be removed or encapsulated. Specify course of action – which is it? What is the scope of work of community room?
Sheet A104 – Missing key notes. Identify all scope components. Does it provide overflow scupper drain per 2018 IBC 1502.2 secondary drains (emergency overflow)?
Sheet A110 – Keynote 8.05 states existing hallway is a “FIRE DOOR” while doesn’t not specify the fire rating. What is the fire rating of existing hallway doors?
Sheet A110 – Keynotes 2.01 states Asbestos Containing Material found while does not state that it’ll be removed or encapsulated. Specify course of action – which is it?
Sheet A110 – No finish schedule provided?
Sheet A201 and A202 – Keynote 2.17 states to “REMOVE EXISTING EXTERIOR CLADDING” while code analysis states that this is fire rated wall. Provide new fire rated stucco exterior wall to show how fire protection integrity is maintained.
Sheet A301 – Provide new TPO roofing details at parapet edge and penetrations. Is if fire rated? Class A roofing? (Specify fire resistance)
Sheet A501 – Secondary drains (emergency overflow) per 2018 IBC 1502.2 missing.
Sheet A501 – Exterior wall and parapet details do not indicate any fire rating.
Sheet A601 – Provide code analysis of exterior openings per 2018 Table 705.8 No sprinklered exterior wall. What is the actual allowable area? Less than 10%? Window details do show existing fire ratings per code analysis (Sheet G003).


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Approved/Subject to field approval


ELECTRICAL REVIEW COMMENTS
Conditionally Approved
E101 ELECTRICAL SITE PLAN: Poor alignment of Keyed Notes.
E110 ELECTRICAL - ENLARGED UNIT PLANS: Missing Keynote #7.


PLUMBING REVIEW COMMENTS:
Denied
First Plumbing review:
1). add a demo plan detail to plan page P101 that correlates with new work detail #3 for the 93 NON ADA units. -IPC 106.3.1
2). Roof plan A104 Keynotes are blank, add the note info that correlates with numbers on the roof plan. -IPC 106.3.1
3). Add scupper & downspout sizing calculations to plan page A501.- IPC 1106.3 1106.5 ( detail #3 states Parapets are new)
4). Add secondary scupper detail to plan A501- IPC 1108


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
06/07/2022 WBERGER1 ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Wyatt Berger
Planner

PROJECT: T22CM03663
4131 N Western Winds Dr
Building interior remodel (1st Review)

TRANSMITTAL DATE: June 7, 2022

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. Zoning has reviewed the building plans for compliance with DP22-0144. Although it appears that the building plans match the DP, Zoning cannot approve the building plan until the DP is approved.

If you have any questions about this transmittal, please contact Wyatt Berger at Wyatt.Berger@tucsonaz.gov.
06/07/2022 ROBERT SHERRY WATER REVIEW Completed
06/07/2022 WBERGER1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
06/21/2022 SSHIELD1 ENGINEERING REVIEW Reqs Change See Zoning comments

Final Status

Task End Date Reviewer's Name Type of Review Description
06/21/2022 VVERA1 OUT TO CUSTOMER Completed