The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T22CM03656
Parcel: 117160300

Address:
102 E COUNCIL ST

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM03656
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/13/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. General: The Site Plan must include information as required by the IBC Section 107.2.6. Please provide.
2. General: Please include a short Project Narrative on the Site Plan. Indicate if this project includes removal of the existing roof sheathing and replacing that with like material. Indicate the new sheathing description, and how that sheathing will be connected to the existing roof framing (include connector size and spacing).
3. General: Please provide written responses to all review comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/13/2022 NGARCIA3 OUT TO CUSTOMER Completed