05/12/2022 PAUL CAMARENA ZONING REVIEW Reqs Change FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: T22CM03609, T22CM03610
ADU/ Carport to bedroom
2202 N LOS ALTOS AV Zoning R-2

TRANSMITTAL DATE:?May ?12,2022
COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1.COMMENT: Draw dimension and label the height of the new structure measured from design grade to top of wall. Label the elevation drawing to show which elevation is for what structure.

The following comments are regarding the ADU.
2. COMMENT: Please provide a parking space per UDC section 6.6.3.B.2: In addition to parking required for the principal use , one parking space shall be provided for the accessory dwelling unit . The parking requirement may be satisfied with available on-street parking or waived if the site is within ΒΌ mile walking distance of a transit stop or an enhanced bike route as listed in the Bike Boulevard Master Plan. Parking provided is exempt from Section 7.6.4, Landscape Standards.
3.COMMENT: If the accessory dwelling unit is built as a new structure it must be developed with a high albedo level (>60 SRI) or other cool roof technology per the ICC Green Construction Code. Provide the information noted by the standard above.

If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov
05/12/2022 PCAMARE1 ENGINEERING REVIEW Passed
05/12/2022 PCAMARE1 NPPO REVIEW Passed
06/07/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change Clarify if the proposed bathroom (foundation, wall and roof) is new or existing. Provide appropriate details.

Show an individual accessible water supply shut off for each dwelling unit, P2903.9.1. Water supply for the new bathroom attached to the existing dwelling may not pass through another (proposed) dwelling.

Clarify the location of panel "C". The Outdoor Lighting Plan shows the panel on the proposed building rather than the bedroom addition.