Permit Number: T22CM03597
Parcel: 133201090

Address:
836 N CORINTH

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM03597
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/11/2022 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T22CM03597
836 N Corinth – R-1
Detached Gym, Bath & Storage Addition (1st Review)

TRANSMITTAL DATE: May 11, 2022

Resubmit revised drawings and a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the R-1 zone (UDC 4.7.8). A single-family residence is permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.5 - .9.

1. Provide a lot coverage calculation that meets the requirements of UDC Article 6.4.3 and the example shown on the Residential Plot Plan Requirements found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf,

2. Per UDC Article 6.6.3.D Accessory structures, except for accessory dwelling units, shall not exceed 12 feet in height, unless attached to a principal structure. Building height is measured per UDC Article 6.4.4, provide a height dimension from design grade to the midpoint of the pitched roof. If this height exceeds 12’-0” a Board of Adjustment for Variance will need to be submitted and approved prior to approval of this permit.

3. Per UDC Article 6.6.3.E The total gross floor area (gfa) of all accessory structures shall not exceed 50% of the gfa of the principal structure. Clearly demonstrate that the proposed detached accessory structure does not exceed the 50% GFA of the main dwelling.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
05/11/2022 SSHIELD1 NPPO REVIEW Passed
05/12/2022 SSHIELD1 ENGINEERING REVIEW Passed
05/16/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM03597


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
Structural calculation – City of Tucson Amendments to the 2018 International Building Code Section 1609.1.1 states Risk Category IV – 115 mph wind load while structural calculation code data shows as wind load of 105 MPH similar. City of Tucson Amendments to the 2018 International Residential Code Table R301.2(1) sets wind speed at 115 mph 3 second gust. Sheet S1.0 A. design criteria sets wind speed at 105 MPH. Please clarify discrepancies.
Sheet S1.2 – Ceiling joist schedule is shown but ceiling framing plan is missing.


BUILDING REVIEW COMMENTS:
Denied
Cover Sheet – Provide general project information such as location map, fire sprinklers and fire alarm info. (None?) Cover sheet only shows rendering without title block.
Sheet G1.0 – A7.1 – Interior finish schedules sheet missing from submitted set.
Sheet A1.0 – Adopted residential building codes and ordinances are: 2018 International Residential Code (IRC); Local Amendments to IRC (www.tucsonaz.gov/pdsd/building-codes); City of Tucson Adopted Design Ordinances – handicap provisions, solar water, photo-voltaic and grey water preparations. (www.tucsonaz.gov/pdsd/building-codes)
Sheet A1.2, A5.2, A5.3 and A5.4 – Provide vapor barrier requirements per S2.0. Identify in foundation details.
Sheet A1.2 – Provide depressed floor slab detail. How deep and slope?
Sheet A2.0 – Specify shower glazing is it safety glazing per 2018 IRC section R308?
Sheet A2.3 – Specify and coordinate steel purlins. Structural sheet S3.0 shows “3. PURLINS PER ARCH.”
Provide Energy Compliance Certificates (REScheck).


MECHANICAL REVIEW COMMENTS:
Denied
Sheet M1.0 – Missing duct layouts, inlet and outlet sizes, equipment locations.
Sheet M1.0 – Missing equipment schedule. To include all equipment, listed and sized.
Sheet M1.0 – Missing ventilation calculations according to 2018 IRC.
Sheet M1.0 – Specify the size of concrete pad for outdoor unit.
Sheet M1.0 – Provide bathrooms-toilet rooms exhaust rate per 2018 IRC Table M1505.4.4


ELECTRICAL REVIEW COMMENTS
Denied
E1.0 – Electrical general notes item 1. Shows the use of “2018” National Electrical Code. City of Tucson adopts 2017 NEC.
E1.1 – Incomplete light fixture schedule.
E1.1 – Provide complete electrical load calculations. (N) AC from new sub panel (A) is missing.
E1.1 – Sub panel labeled as 60 AMP while panel schedule shows 100A with 100A bus. Is it incorrect labeling? Sub panel – 100 AMP (extg) also do not match.
E1.1 – Electrical legend shows smoke detector. Is it intended to have smoke detector in the new structure?


PLUMBING REVIEW COMMENTS:
Denied
Sheet P1.0 – Provide riser diagrams from water, wastewater, and vent piping. Show all points of connection to water and sewer lines.
Sheet P1.0 – Provide plumbing fixture schedule.


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov