Permit Number: T22CM03594
Parcel: 133210590

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM03594
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/07/2022 ARUIZ1 OIP REVIEW Completed
08/10/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Completed Activity Number: T22CM03594

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
Provide roof load documentation per 2018 IRC T103.7 (RA103.7). The structural design loads for roof dead load and roof live load shall be clearly indicated on the construction document. Can the existing roof accommodate the new loads?


BUILDING REVIEW COMMENTS:
Denied
Show access and pathways to the new PV modular per 2018 IFC section 1204.2.1.

MECHANICAL REVIEW COMMENTS:
N/A

ELECTRICAL REVIEW COMMENTS
Denied
Show access and pathways to the new PV modular per 2018 IFC section 1204.2.1.


PLUMBING REVIEW COMMENTS:
N/A

If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
07/07/2022 VVERA1 OUT TO CUSTOMER Completed