Permit Number - T22CM03591
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/03/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change A vent has not been added to the sump pump. [Second comment: A vent is required for the sump pump. The vent can be connected to other plumbing vents in the building once it is at least 6" above the flood rim of the highest fixture.] [Initial comment: The vent and the discharge pipe are separate entities and may not be combined. Reference: Section 303.2, IPC 2018.]