Review Date Reviewer's Name Type of Review Description Status Comments
05/11/2022 WBERGER1 ZONING REVIEW Approved
05/11/2022 WBERGER1 ENGINEERING REVIEW Passed
05/11/2022 WBERGER1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/23/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/25/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
05/25/2022 ROBERT SHERRY WATER REVIEW Completed
05/26/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The vent and the discharge pipe are separate entities and may not be combined. Reference: Section 303.2, IPC 2018.
2. Revise detail 5/A6 (waste and vent riser diagram) to provide a full-open valve on the discharge side of the check valve. Note that the manufacturer's installation instructions also call for a union on the discharge pipe. Reference: Sections 303.2 and 712.2, IPC 2018.
3. Verify that there is access for the check and full-open valves outside of the sump. Reference: Section 712.2, IPC 2018.
4. Connect the effluent of the sump pump to the sanitary drain system as described in Section 712.3.5, IPC 2018.
5. Verify that the connection point for the 1.5" forced waste pipe to the building drainage system is at least 10 pipe diameters from the base of any soil or waste stack or any fixture drain. Reference: Section 712.3.5, IPC 2018
06/06/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/24/2022 JVINCEN1 FIRE REVIEW Approved