Permit Number: T22CM03488
Parcel: 141153540

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM03488
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/09/2022 WBERGER1 ENGINEERING REVIEW Passed
05/09/2022 WBERGER1 ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Wyatt Berger
Planner

PROJECT: T22CM03488
8140 S Houghton Rd #180
TI: Restaurant (1st Review)

TRANSMITTAL DATE: May 9, 2022

Please resubmit updated drawings along with a detailed comment response letter, which states how all zoning review comments were addressed.

1. As a new fence with gates is being proposed on this commercial site, a Development Package (DP) that meets the minimum requirements of the Checklist for Minor Changes to Commercial/Industrial sites must be submitted and approved. This checklist can be found at: https://www.tucsonaz.gov/files/pdsd/forms/Minor_Changes_to_Commercial_Industrial_Sites_.pdf.
2. As you are proposing an expansion of a Food Service use with an outdoor patio, demonstrate that 50% or more of all uses within the existing shopping center are not Food Service and Alcoholic Beverage Service uses to comply with parking standards. If more than 50% of all shopping center uses are Food Service and Alcoholic Beverage Service uses, a Development Package is required.

If you have any questions about this transmittal, please contact Wyatt Berger at Wyatt.Berger@tucsonaz.gov.
05/09/2022 WBERGER1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
05/24/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM03488


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Denied
1. Fire protection systems modifications are not shown. 2018 IBC – 901.3. Please indicate that any modifications to fire sprinkler system or fire alarm system will be a deferred submittal before the alteration begins.
2. Fire extinguishers are not shown on plans. 2018 IBC - 906 and NFPA 10 - 6.1.3, 6.1.3.3 & 6.2.1.2. Revise sheet A3 with fire extinguisher locations at exits from areas with maximum travel distance between each not to exceed 75 feet.
3. Fire extinguishers provided for the protection of cooking grease fires shall be of an approved type compatible with the automatic fire-extinguishing system agent and in accordance with International Fire Code. 2018 IBC - 906.4. Revise sheet A3 with location of Type K fire extinguishers in kitchen for grease fires.
4. Every room or space that is an assembly occupancy shall have the occupant load posted in a conspicuous place, near the main exit or exit access doorway from the room or space. 2018 IBC – 1004.9. Revise sheet A3 with location of occupant load signage on egress/floor plan.
5. Missing exterior lighting at exit discharge. 2018 IBC – 1008.2.3. Revise plans to include exterior lighting at man door (s).
6. Missing emergency lighting in aisle, stairways, corridors, exit passageway, exit discharge and exterior landings for buildings that require two or more exits. 2018 IBC – 1008.3.2. Revise plans to include emergency lighting at exterior landings of exit door(s).
7. Missing minimum clear opening width of 32 inches with door open 90 degrees, including gates. 2014 InBC - 1010.1.1. Revise plans with gate clear opening dimension.
8. A tactile exit sign stating EXIT and complying with Chapter 11 shall be provided adjacent to each door to exit stairway and the exit discharge. 2018 IBC 1013.4. Revise plans to indicate locations of tactile exit signs and sign mounting height details.


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
1. Commercial cooking appliances that required a Type I hood shall be provided with an approved automatic fire suppression system. 2018 IMC – 509.1. Provide plans to show compliance with this section or indicate as deferred separate submittal.


ELECTRICAL REVIEW COMMENTS
Denied
1. 2018 IEBC Section 807.3.5 - Provide illumination on the exterior of any egress doors.


PLUMBING REVIEW COMMENTS:
Approved

If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
05/25/2022 JPEELDA1 FIRE REVIEW Reqs Change 1. Fire protection systems modifications are not shown. 2018 IBC – 901.3. Please indicate that any modifications to fire sprinkler system or fire alarm system will be a deferred submittal before the alteration begins.
2. Fire extinguishers are not shown on plans. 2018 IBC - 906 and NFPA 10 - 6.1.3, 6.1.3.3 & 6.2.1.2. Revise sheet A3 with fire extinguisher locations at exits from areas with maximum travel distance between each not to exceed 75 feet.
3. Fire extinguishers provided for the protection of cooking grease fires shall be of an approved type compatible with the automatic fire-extinguishing system agent and in accordance with International Fire Code. 2018 IBC - 906.4. Revise sheet A3 with location of Type K fire extinguishers in kitchen for grease fires.
4. Every room or space that is an assembly occupancy shall have the occupant load posted in a conspicuous place, near the main exit or exit access doorway from the room or space. 2018 IBC – 1004.9. Revise sheet A3 with location of occupant load signage on egress/floor plan.

Questions:
Jennifer Peel-Davis
Jennifer.Peel-Davis@tucsonaz.gov
520-837-7033Fire Plans Examiner
06/02/2022 ROBERT SHERRY WATER REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
06/03/2022 VVERA1 OUT TO CUSTOMER Completed