Permit Number: T22CM03472
Parcel: Unknown

Address:
4054 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM03472
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/09/2022 WBERGER1 ZONING REVIEW Approved
05/09/2022 WBERGER1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/12/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM03472

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
Sheet A400 – Detail 02: Provide bracing size and spacing.
Sheet A400 – Detail A: Provide UL Design No.U465 one hour rated detail and penetration fire protection details


BUILDING REVIEW COMMENTS:
Denied
General comment: Provide complete documents per City of Tucson checklist.
https://www.tucsonaz.gov/files/integrated-planning/PDSD/Fill_-_Commercial_Submittal_Requirements_-_January2020.pdf
Sheet A000 – Provide complete applicable codes. Accessibility codes indicates “2011 OBC 2009 117.1 ANSI” Is this Ohio Building Code? “ICC A117.1 – 2009 Accessible and Usable Buildings and Facilities (by reference)” is used in local amendment.
Sheet A000 – Provide fire alarm requirements per NFPA 72. Does this include fire alarm scope? Is it differed submittal? Is sprinkler system under separate permit?
COMcheck – Provide Energy Compliance Certificates per checklist.
Sheet A000 – Provide existing occupancy type. Sheet provide 1st Tenant Improvement, shell permit number referenced in plan to clarify.
Cover sheets – Provide legend of symbols and abbreviations per Checklist.
Sheet A015 – “2012 ADA Standards for Accessible Design for Public Accommodations and Commercial Facilities: Title lll” is shown. “ICC A117.1 – 2009 Accessible and Usable Buildings and Facilities (by reference)” is used in local amendment.
Sheet A015 and A016 – Remove details not applicable for this project and clarify the scope of work per 2018 IBC 107.2.1. Misleading detail scope such as parking shown.
Sheet A018 – Section 08111 shows standard steel doors and frames not overhead door. Overhead door does not qualify as means of egress door per 2018 IBC 1008.
Sheet A020 – Show partial demolition of existing walls above removal of existing slab area or show how slab demolition is performed while keeping existing walls. Explain how existing exterior wall is kept while removing existing slab under. Provide exterior floor information connecting to existing sanitary sewer. Is there a walkway? Is it on grade?
Sheet A020 – Provide occupancy information of existing space. Is this 1st tenant improvement which had shell permit number?
Sheet A100 – New drinking fountain is protruding object as indicated in sheet A015 section 307.
Sheet A100 – Show new louvers and provide exterior elevation. Permit application indicates “No” exterior work. Please clarify and coordinate permit application and all drawing disciplines.
Sheet A101 – Identify floor component in entry. Is this a recessed floor mat? If so, provide recessed floor mat detail.
Sheet A101 – The project is at 4,070 SF provide vestibule per 2018 IECC C402.5.7 or show compliance with exception sections.
Sheet A101 – Section 08111 shows standard steel doors and frames not overhead door. Overhead door does not qualify as means of egress door per 2018 IBC 1008. Provide explanation or exception code section.
Sheet A101- Provide locations of fire extinguisher per 2018 IBC 906.
Sheet A101 – Provide access space dimensions and means of egress distance and methods from behind the dryers DE650S and DE635S. Show compliance with 2018 IMC 306 access and service space. Coordinate new mechanical louvers with disciplines.
Sheet A101 – Show ADA compliance such as wash-dry fold counter details and floor clear space. Are there ADA compliant folding bench?
Sheet A101 – Show common path of egress travel distance from Office per 2018 IBC 1006.2.1 and exit access travel distance per 2018 IBC 1017.2.
Sheet A100 – Show interior elevation of utility room how new tankless water heaters provides access per 2018 IMC 306 access.
Sheet A400 – Section F shows overhead door while not shown in specification sheet. Section 08111 shows standard steel doors and frames not overhead door. Overhead door does not qualify as means of egress door per 2018 IBC 1008. Provide explanation or exception code section.
Sheet 401 – Provide exterior elevation that shows new louvers.


MECHANICAL REVIEW COMMENTS:
Denied
Sheet M1.0 – Note indicates “no site information provided to design team. Design assumes the existing HVAC systems and ductwork will be reused.” Verify and clarify the existing/new duct scope.
Sheet M2.0 – 01 and 02 details: Provide roof penetration details and waterproofing specification.
Sheet MEP1.0 – Fire protection system is hatched. Clarify this: Omit items that does not apply to scope. Is fire protection system per separate permit?


ELECTRICAL REVIEW COMMENTS
Denied
Sheet E1.0 – Show new mechanical louvers. Panel ‘L4’ is located at new louver. Show how overlapping louver and electrical panel can work.
Sheet E3.0 – 02 One-line riser diagram: Specify the exact size of existing C/T metering cabinet. Does it require upsize to 400A?


PLUMBING REVIEW COMMENTS:
Denied
Sheet P1.0 – Plumbing fixture schedule shows “Replace existing fixture if in too poor condition.” Specify replacing plumbing fixtures or not.
Sheet P3.0 – 01 plumbing waste riser diagram: Specify existing sanitary line.
Sheet P4.0 – Provide complete gas plan, calculation and individual pipe length, pipe sizes, and loads per checklist.
Sheet P4.0 – 03 typ. Dual tankless gas water heater detail: Show how this works right at utility sink and accessible per 2018 IMC 306 access.


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
05/14/2022 JVINCEN1 FIRE REVIEW Reqs Change Resolve building comments.

john vincent
john.vincent@tucsonaz.gov
520-349-5581
06/01/2022 ROBERT SHERRY WATER REVIEW Completed
06/29/2022 PCAMARE1 ENGINEERING REVIEW Reqs Change This project is within a mapped flood hazard area and requires a Floodplain Use Permit (FUP.)
Please start a new FUP at our permit application web page: https://docs.tucsonaz.gov/Forms/tucsonpermitapp.
Instructions:
• Is this for a new or existing activity application? – Please select New Application.

• Submission Type – Select Floodplain Use Permit.

• Project Name – Enter a name for your project.

• Select Street Name from the list. You can type the first two letters or number to get closer to your choice in the list. Then select the rest of the address in the boxes provided.

• Type of Permit – Select Commercial or Residential (Residential is for work on single family residences and duplexes.)

• Complete the Applicant Info.
• Complete the Contractor, Owner and Architect/Engineer sections as applicable.

• Supporting Documentation Upload – Provide a complete cost estimate for the project. You may also provide additional documents you think will be helpful.

• Sign the application and submit.

• You will be given an activity number for your submittal. Please copy and send this number back to us so we can continue the review.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/29/2022 NGARCIA3 OUT TO CUSTOMER Completed