Review Date Reviewer's Name Type of Review Description Status Comments
06/29/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM03438

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
Structural documents – Provide roof load documentation per 2018 IRC T103.7 (R103.5). The structural design loads for roof dead load and roof live load shall be clearly indicated on the construction documents. Can the existing roof accommodate new applied loads?


BUILDING REVIEW COMMENTS:
Denied
Sheet PV-2 – Legend shows fire access (4’ width typical) while roof plan and modules shows at 3’-0” so coordinate document. Modules may not fit on roof at 4’ width as indicated.


MECHANICAL REVIEW COMMENTS:
N/A

ELECTRICAL REVIEW COMMENTS
Denied
Sheet PV-2 – Legend shows fire access (4’ width typical) while roof plan and modules shows at 3’-0” so coordinate document. Modules may not fit on roof at 4’ width as indicated.


PLUMBING REVIEW COMMENTS:
N/A

If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
07/15/2022 ARUIZ1 OIP REVIEW Reqs Change TRANSMITTAL DATE: July 15, 2022

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed.

COMMENT: Residential has reviewed the plan and cannot approve at this time. Please address the following comments

COMMENT: After comparing the aerials to the plot plan it has come to my attention that the roof structure changed around 2005-2008. After researching PRO there are records for a permit pending approval. Permit T20CM07897. Before moving forward with Solar you will need to complete permits for the work without permits on the property.

COMMENT: Zoning will review the application on the next submittal

If you have any questions about this transmittal, Contact Angie.Ruiz@Tucsonaz.gov any time during the week by email

Final Status

Task End Date Reviewer's Name Type of Review Description
07/18/2022 NGARCIA3 OUT TO CUSTOMER Completed