Permit Number: T22CM03433
Parcel: 117060640

Address:
219 N 3RD AV 129

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM03433
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/06/2022 WBERGER1 ZONING REVIEW Approved
05/06/2022 WBERGER1 ENGINEERING REVIEW Passed
05/06/2022 WBERGER1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/18/2022 JVINCEN1 FIRE REVIEW Approved
05/19/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/23/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Show that the proposed replacement rooftop units meet the requirements of Sections C403.3, C403.4, and C403.5 (e.g. provide the mechanical compliance certification from COMcheck). Reference: Section C501.4, International Energy Conservation Code 2018.
2. Provide heating and cooling load calculations to justify the heating/cooling capacity of the specified HVAC unit. Reference: Section C403.1.1 and C502.2.3, IECC 2018.
05/23/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
05/23/2022 ROBERT SHERRY WATER REVIEW Completed
06/02/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved