Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T22CM03419
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/16/2022 | JPEELDA1 | FIRE | REVIEW | Reqs Change | Plans show that they have a 36" fire setback. IFC 2018, Chapter 12, Section 1204.3.1-1204.3.2 shall be met. You are stating that this is a house but is an office- owner shall also obtain a COFO for change of occaupnacy to be code compliant. We will not accept the IRC and or R-3 rules. Questions: Jennifer Peel-Davis Jennifer.Peel-Davis@Tucsonaz.gov 520-837-7033 Fire Plans Examiner |
| 08/31/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | There was no written response located in the 2nd submittal and the previous electrical review comment is not addressed. |
| 10/07/2022 | JGARCIA1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | Previous review comments not addressed. See below. 1. General: All sheets in this submittal must be sealed, signed, and dated by a registered design professional per the IBC Section 107. Please provide. 2. General: Please provide structural calculations that verify the existing roof is capable of supporting the new loads from the PV system. These calculations must be sealed, signed, and dated by a registered design professional. 3. General: Please provide written responses to all review comments. |