Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Permit Number - T22CM03413
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/05/2022 | PAUL CAMARENA | ZONING | REVIEW | Reqs Change | FROM: Paul Camarena PDSD Zoning Review Section PROJECT: T22CM03413 Porch 2870 W PLACITA DE JUAN Zoning R-1 TRANSMITTAL DATE: May 5,2022 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1.COMMENT: Provide a Residential Plot Plan that meets the requirements found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf. This shall in include: a. Lot coverage calculation that meets the requirements of UDC Article 6.4.3 & the example shown on the residential plot requirements. b. Actual setback dimension. c. All Utility lines d. Property line distances e. Zoning of adjacent parcels 2.COMMENT: Draw dimension and label the height of the structure measured from design grade to top of wall in order to verify the setbacks for the porch If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov |
| 05/05/2022 | PCAMARE1 | NPPO | REVIEW | Passed | |
| 05/17/2022 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | T22CM03413 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide an updated complete plan set with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. GENERAL REQUIREMENTS: The City of Tucson adopted the 2018 IRC with amendments on 1/1/2019. Show the current code reference on the plans. Sample plans are available at https://www.tucsonaz.gov/pdsd/residential-permits SITE PLAN: 1. Indicate the location of buildings and any utilities supporting or effecting the proposed structure such as gas lines. FOUNDATION PLAN: 1. Dimension the footing length, width, and depth into undisturbed soil for each footing type and condition, R403.1. Show the minimum 12” reinforced footing depth below the undisturbed ground surface R403.1. Show rebar reinforcement with 3” clearance from earth, R403.1.3.5.3. Provide ½” anchor bolts with 7” embedment, R403.1.6. FRAMING PLAN: 1. Provide a complete roof framing plan with beams and rafters sized with appropriate load carrying capacity, R301.1. Show beam size. SECTIONS - DETAILS: 1. Show the Post Section Detail with #4 rebar in the footing, R403.1. 2. Notate and specify the size of post base with 1” standoff above concrete, R317.1.4 exception 1. 3. Show roof (uplift resistance) rafter fasteners (H2.5) with appropriate uplift capacity, R802.11 amended. 4. Show connection at dwelling with fasteners (rafter on top plate with H2.5 or ledger connection to load bearing wall). 5. Show the rafters with bearing contact to a wall top plate structure with foundation, R502.6 & R802.6. Replace the rafter connection to fascia or provide a registered Arizona engineer design analysis with seal. ELECTRICAL PLANS: 1. Show alteration of any lighting and receptacle outlets. Please contact the plans reviewer if you have any questions: Ken Van Karsen 520 837-4912 City of Tucson Residential Plan Review |
| 05/24/2022 | PCAMARE1 | ENGINEERING | REVIEW | Passed |