Permit Number: T22CM03409
Parcel: 134071530

Address:
8508 E KENT PL

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM03409
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/22/2022 RPARSON1 OIP REVIEW Completed
07/07/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Approv-Cond Activity Number: T22CM03409

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Approved

MECHANICAL REVIEW COMMENTS:
N/A

ELECTRICAL REVIEW COMMENTS
Conditionally Approved
1. Back-fed breaker exceeds 120% of busbar rating. 2017 NEC - 690.64 & 705.12. The plans indicate that the main panel has a rating of 200amps, but does not indicate if this is also the bus rating. If the bus is rated at 225amps, the 50 amp back-fed breaker is sized correctly.


PLUMBING REVIEW COMMENTS:
N/A

If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
07/07/2022 VVERA1 OUT TO CUSTOMER Completed