| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/22/2022 | RPARSON1 | OIP | REVIEW | Completed | |
| 07/12/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Approv-Cond | Activity Number: T22CM03394 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Approved BUILDING REVIEW COMMENTS: Approved MECHANICAL REVIEW COMMENTS: N/A ELECTRICAL REVIEW COMMENTS Conditionally Approved 1. Back-fed breaker exceeds 120% of busbar rating. 2017 NEC - 690.64 & 705.12. The plans indicate that the main panel has a rating of 125amps, but does not indicate if this is also the bus rating. If the bus is rated at 150amps, the 30 amp back-fed breaker is sized correctly. PLUMBING REVIEW COMMENTS: N/A If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |