Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T22CM03386
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/04/2022 | VFLORES1 | PIMA COUNTY - ADDRESSING | PIMA COUNTY - ADDRESSING | Reqs Change | PLEASE CONTACT PC ADDRESSING BUILDING NUMBER NEEDS TO BE ASSIGNED PRIOR TO ISSUANCE Ph# 520-724-9512, EMAIL:ADDRESSING@PIMA.GOV |
| 05/19/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T22CM03386 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Denied 1. Provide a copy of the geotech report mentioned in structural notes on S-drawings. 2. Please have your geotech engineer address foundation drainage issue, whether foundations need to be designed for ground water pressure or not. 3. The design wind speed to be considered for wind uplift is 110 mph, this information is missing from the design documents. 4. Design for connectors is not provided, please use a minimum of 110 mph design wind speed when designing connectors for wind uplift. 5. Weight of masonry wall considered in seismic base shear calculations seems to be low, a value of 66psf is used whereas a value of 80 psf is used normally, please explain. BUILDING REVIEW COMMENTS: Denied 1. General: Provide full manufacturer specifications for the lift. 2. Sheet A0.1: Provide an architectural site plan that includes all accessible routes and parking. 3. Sheet A0.1: The allowable area provided is incorrect. Provide the correct allowable area in accordance with Table 506.2 and Type II construction. 4. Sheet A0.1: The allowable height provided is incorrect. Provide the correct allowable height in accordance with Table 504.3 and Type II construction. 5. Sheet A0.1: The allowable stories provided is incorrect. Provide the correct allowable stories in accordance with Table 504.4 and Type II construction. 6. Sheet A0.1: This sheets states that no occupancy separation is required. It's assumed that separated occupancies is the desired compliance path. Occupancy separation is required between a B occupancy and U occupancy. Provide a correct occupancy separation in accordance with Table 508.4. 7. Sheet A1.1: Upon further clarification of the occupancy separations door D-13 will required to be protected in accordance with Section 716. 8. Sheet A1.2: Upon further clarification of the occupancy separations window W-18 will required to be protected in accordance with Section 716. 9. Sheet A1.3: Indicate on the egress plans the location of exit signage and egress illumination in accordance with Sections 1008 and 1013. 10. Sheet A1.3: Indicate on the egress plans the location of exit signage and egress illumination in accordance with Sections 1008 and 1013. 11. Sheet A1.9: The lavatory is in the clear floor space of the water closet. Additionally, the ADA restroom does not meet the minimum clear floor spaces in accordance with Section 604.3.2 of the 2010 ADAAG. MECHANICAL REVIEW COMMENTS: Denied 1. Show how you are bringing in ventilation air to office through DHP#2 sheet M1.0 (IMC2018,106.3.1) 2. Show how you are bringing outside air for ventilation for storage room #109 DHP#1 sheet M1.0 (IMC2018,106.3.1) 3. Provide calcs for treatment room area 2 you only got for treatment #1 sheet M1.0 (IMC2018,403.3.1.1) 4. Offices shall be labeled according to their room numbers their is no office #1,2 or 3 on the plans sheet M1.0 (IMC2018,106.3.1) ELECTRICAL REVIEW COMMENTS Approved E2.1 Lighting Plan First Floor: Missing Keynote #7 PLUMBING REVIEW COMMENTS: Denied First Plumbing Review: 1). Plan page A1.10 Needs to include gutter & downspout sizes with calculations - IPC 1106.1, 1106.3, 1106.6 2). Due to multiple washing machines regardless of type, each will need to discharge thru an lint interceptor. update plan pages P1.0, P2.0, P3.0. -IPC 1003.6 3). Add gas piping distance to Gas diagram A note #2. -IFGC 402.4 4). Add backflow device to detail 215 on plan page P2.0. -IPC 608.3 5). Per the Gas water heater installation manual there is not an concentric vent/intake kit option as shown on plan page M1.0 #6. This Unit has single exhaust & optional separate piped air intake or install high/low combustion air grills. Update plan page M1.0 to match this gas water heater exhaust & intake requirements. -IFGC 304, 305.1 6). install both building drains upstream of back water valve on plan page P1.0 -IPC 714.1 7). This occupancy type and load requires a high/low drinking fountain & service sink update all affected floor plan & Plumbing pages. -IPC 403.1 8). Add ASSE 1070 mixing valves to Lavs on plan page P3.0. -IPC 419.5 9). Add Fixture spacing measurements to plan page A1.9 -m IPC 404.2, 405.3.1 10). Upload complete site utility piping for continuation of water service, sewer & storm as stated on plan pages P1.0 & P1.2 If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
| 05/20/2022 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: T22CM03386 – DP22-0117 8300 E Tanque Verde Rd Animal Services - Expansion (1st Review) TRANSMITTAL: May 20, 2022 This site is located in the SR zone (UDC 4.7.4). Animal Services is a permitted use in this zone (Table 4.8-1) subject to Use Specific Standard 4.9.4.D.5. 1. Zoning has reviewed the building plans for compliance with DP22-0117 and although it appears that the plans match the DP until at least one review of the DP is complete Zoning cannot verify if all UDC requirements are met. Until DP22-0117 is approved Zoning cannot approve the building permit. If you have any questions about this transmittal, please contact Nicholas Ross at Nocholas.Ross@tucsonaz.gov. |
| 05/20/2022 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 05/26/2022 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 06/13/2022 | JPEELDA1 | FIRE | REVIEW | Reqs Change | Provide documentation that the new building meets the requirements of IFC 2018, Chapter 5, 507.5.1 of 400'. Provide a diagram to TFD from the nearest hydrant to the furthest part of the addition as the hose lays and the distance. If the distance exceeds 400' a fire sprinkler system shall be installed. Second floor appears to be open and possible use for a sleeping area for staff to watch the animals at night (on call room). Please clarify if this is the use. If this is the use it shall be changed from a B to an R Occupancy and meet those separation requirements. Questions: Jennifer Peel-Davis Jennifer.Peel-Davis@tucsonaz.gov 520-837-7033 Fire Plans Examiner |
| 06/21/2022 | SSHIELD1 | ENGINEERING | REVIEW | Reqs Change | See Zoning comments |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/21/2022 | VVERA1 | OUT TO CUSTOMER | Completed |