Permit Number: T22CM03368
Parcel: 122183840

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM03368
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/04/2022 PAUL CAMARENA ZONING REVIEW Approved
05/04/2022 PCAMARE1 NPPO REVIEW Passed
05/19/2022 PCAMARE1 ENGINEERING REVIEW Reqs Change This project is within a mapped flood hazard area and requires a Floodplain Use Permit (FUP.)
Please start a new FUP at our permit application web page: https://docs.tucsonaz.gov/Forms/tucsonpermitapp.
Instructions:
Is this for a new or existing activity application? – Please select New Application.

Submission Type – Select Floodplain Use Permit.

Project Name – Enter a name for your project.

Select Street Name from the list. You can type the first two letters or number to get closer to your choice in the list. Then select the rest of the address in the boxes provided.

Type of Permit – Select Commercial or Residential (Residential is for work on single family residences and duplexes.)

Complete the Applicant Info.
Complete the Contractor, Owner and Architect/Engineer sections as applicable.

Supporting Documentation Upload – Provide a complete cost estimate for the project. You may also provide additional documents you think will be helpful.

Sign the application and submit.

You will be given an activity number for your submittal. Please copy and send this number back to us so we can continue the review.
06/03/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Approv-Cond Activity Number: T22CM03368

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Conditionally Approved
Roof trusses to be provided as a differed submittal.

BUILDING REVIEW COMMENTS:
Conditionally Approved
1. All work shall be in accordance with the 2018 IRC and the adopted codes of the City of Tucson.
2. The soil beneath the slab and around the footing shall be treated for termites prior to the placement of the concrete for the shed. 2018 IRC R318.
3. All wood framing installed in contact with the concrete shall be pressure treated.

MECHANICAL REVIEW COMMENTS:
Conditionally Approved
No mechanical work has been included with this submittal.

ELECTRICAL REVIEW COMMENTS
Conditionally Approved
No electrical work has been included with this submittal.

PLUMBING REVIEW COMMENTS:
Conditionally Approved
No plumbing work has been included with this submittal.


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov