Permit Number: T22CM03353
Parcel: 136100960

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM03353
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/03/2022 VFLORES1 PIMA COUNTY - ADDRESSING PIMA COUNTY - ADDRESSING Reqs Change PLEASE CONTACT PC ADDRESSING BUILDING NUMBER NEEDS TO BE ASSIGNED PRIOR TO ISSUANCE Ph# 520-724-9512, EMAIL:ADDRESSING@PIMA.GOV
05/18/2022 PAUL CAMARENA ZONING REVIEW Reqs Change REVIEW TRANSMITTAL

FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: T22CM03347, T22CM03348,T22CM03349, T22CM03350, T22CM03351 T22CM03352, T22CM03353, T22CM03354, T22CM03355, T22CM03356, T22CM03357, T22CM03358, T22CM03359, T22CM03360
Building plans (1st Review)
2885 S HOUGHTON RD Zoning SR

TRANSMITTAL: May 18, 2022

1. Zoning has reviewed the building plans for compliance with the associated unapproved Development Package DP21-0042. Zoning cannot approve the building plans until the DP is approved.

2.COMMENT: It appears that the DP and the building plan do not match, please clarify

If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov
05/18/2022 PCAMARE1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
05/19/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM03353/BLDG #7, T22CM03348/BLDG #2, T22CM03349/BLDG #3, T22CM03350/BLDG #4, T22CM03351/BLDG #5, T22CM03352/BLDG #6, T22CM03347/BLDG #1, T22CM03354/BLDG #8, T22CM03355/BLDG #9, T22CM03356/BLDG #10, T22CM03357/BLDG #11, T22CM03358/BLDG #12, T22CM03359/BLDG #13, T22CM03360/BLDG #14,

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. The Structural Calculations submitted references International Building Code 2012 on pages 20 of 29 to 25 of 29. The City of Tucson, AZ is on IBC 2018. Revise the Calculations and resubmit


BUILDING REVIEW COMMENTS:
Denied
1. Sheet G001: The allowable and actual height and areas provided do not match Table 506.2. Provide a breakdown of each building's allowable and height and area.
2. Sheet G001: The statement regarding the separation of occupancies does not occur in this project. No R-3 occupancies occur. Remove or correct the statement.
3. Sheet G001: The statement regarding 1/2 hour fire walls is not correct and does not occur in this project. Remove this incorrect statement.
4. Sheet G001: The occupant load factor used for office is incorrect. Provide a corrected occupant load calculation for each building in accordance with Table 1004.5.
5. Sheet G001: It's unclear if sprinkler systems will be required. Provide a area breakdown for each building in accordance with previous comments.
6. Sheet G001: The exit access travel distance is stated as 250', however, there is no indication that any of the buildings are sprinklered. Therefore, exit access travel distance would be 200'. Provide clarification and correction in accordance with Table 1017.2.
7. Sheet G001: The allowable and actual number of stories states that there are two stories. However, none of plans indicate two stories is present on any of the building. Provide clarification or provide the missing floor plans.
8. Sheet G002: The occupant load calculations provided on the life safety plan is incorrect. Provide a corrected occupant load calculation in accordance with Table 1004.5.
9. Sheet G002: No egress illumination provided on the egress plan. Provide the location of all egress illumination on the egress plans in accordance with Section 1008.
10. Sheet G002: Provide clarification as to why buildings #1 and #2 are considered separate buildings and not one. Is this one building with separated occupancies in accordance with Section 508? Additional clarification required. If two buildings are desired; then a fire wall complying with Section 706 would be required.
11. Sheet G003: No egress illumination provided on the egress plan. Provide the location of all egress illumination on the egress plans in accordance with Section 1008.
12. Sheet A002: The north walls of buildings #3 and #5 are required to have a minimum fire resistance rating. No wall tags have been provided for these walls in correlation to the wall types found on Sheet A021. Provide correctly labeled walls with the required fire resistance rating in accordance with Table 602.
13. Sheet A002: The east walls of buildings #3 and the west wall of building #5 are required to have a minimum fire resistance rating. No wall tags have been provided for these walls in correlation to the wall types found on Sheet A021. Provide correctly labeled walls with the required fire resistance rating in accordance with Table 602.
14. Sheet A201: Some walls are missing wall tags. Provided correctly labeled wall tags for all walls present.
15. Sheet A202: Some walls are missing wall tags. Provided correctly labeled wall tags for all walls present.
16. Sheet A203: Some walls are missing wall tags. Provided correctly labeled wall tags for all walls present.


MECHANICAL REVIEW COMMENTS:
Denied
1. Provide plans for mechanical equipment for the 5 retail spaces showing ductwork and all other pertinent information. this is not a core and shell, it's a complete build out sheet M201 (IMC2018,106.3.1)
2. Provide ventilation air to storage room in an approved manner sheet M201 (IMC2018,403.3.1.1)
3. Provide return air to each room sheet 201 (IMC2018,403.1)
4. Provide ventilation air schedule for building 1 sheet M201 (IMC2018,403.3.1.1)
5. Provide 1,288 cfm of ventilation air you got 900 cfm coming in the square footage of building 4 is 21,460 square feet sheet M202 (IMC2018,403.3.1.1)
6. Provide 859 cfm of ventilation air you got 600 cfm coming in the square footage of building 12 is 14,315 square feet sheet M203 (IMC2018,403.3.1.1)
7. Provide a permanent means of access to equipment on building 1 & 2 where roof is above 16 feet from grade (IMC2018,306.5)


ELECTRICAL REVIEW COMMENTS
Denied
Need to provide interior lighting Comchecks for buildings with lighting. Need to provide site lighting calculation per Tucson requirements.
E201 FIRST FLOOR POWER PLAN BUILDINGS 1 AND 2: Should provide a service receptacle in each Retail/Office space.
E207 FIRST FLOOR POWER PLAN BUILDINGS 9, 10 AND 11: Keynote #2 not used.
E301 FIRST FLOOR LIGHTING PLAN BUILDINGS 1 AND 2: Other codes may require that you install some lighting, emergency lighting, and a receptacle in the Retail/Office areas as a Core and Shell type design.
E401 FIRST FLOOR SYSTEMS PLAN BUILDINGS 1 & 2:
Need pull station at egress of storage office.
Need to confirm Retail/Office areas will be sprinklered or provide smoke detectors in each. Should provide a horn and strobe in each Retail/Office area.
E403 FISRT FLOOR SYSTEMS PLAN BUILDING 4: Need pull stations at each egress.
E801 DETAILS, SCHEDULES & RISER DIAGRAMS: All of the Mini substations are called out to be 15 KVA 1 phase. The primary should be furnished with 40 amp minimum CBs to avoid nuisance trips. Or your design could be for 5 KVA transformers (CAD error), which make the 20 amp selection correct. Coordinate design issue to correct for one or the other. Panel schedules imply 5 KVA for mini subpanel.
E902 SCHEDULES:
All of the secondary 20A mini subpanels (20 amp is on the primary) could have 30 amp (or larger) MCBs per NEC.
Should attempt to balance loads on LB4.
E903 SCHEDULES: All of the secondary 20A mini subpanels (20 amp is on the primary) could have 30 amp (or larger) MCBs per NEC.


PLUMBING REVIEW COMMENTS:
Denied
First Plumbing review:
1). Plumbing plan P200 doesn't correlate with floor Plan page A201, show all plumbing fixtures & sanitary/venting piping illustrations. -IPC 106.3.1
2). illustrate water piping to all fixtures on plan page P201 to correlate with fixtures shown on A201 floor plan. -IPC 106.3.1
3). Plan page P201 shows 3" vent that doesn't Correlate with plan page P200 shows 1.25" vent.. -IPC 106.3.1
4). plan page P601 fixture schedule missing breakroom sink information, break room sink is shown on floor plan A201. -IPC 106.3.1
5). This facility requires a service sink & high low drinking fountain- -IPC 403.1 Update all affected pages.
6). Add storm conductor sizing calculations to plan page P201. -IPC 1106.2
7). Add the types of piping materials to be used to plan page P601. -A106.3.1
8). Provide civil plans to show continuation of water, storm, & sanitary systems, and any onsite RV dump stations & water outlets. -IPC 106.3.1


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
05/25/2022 ROBERT SHERRY WATER REVIEW Reqs Change
06/09/2022 JPEELDA1 FIRE REVIEW Reqs Change Sheet G001: The allowable and actual height and areas provided do not match Table 506.2. Provide a breakdown of each building's allowable and height and area.
Sheet G001: The statement regarding 1/2 hour fire walls is not correct and does not occur in this project. Remove this incorrect statement.
Sheet G001: The occupant load factor used for office is incorrect. Provide a corrected occupant load calculation for each building in accordance with Table 1004.5.
Sheet G001: It's unclear if sprinkler systems will be required. Provide a area breakdown for each building in accordance with previous comments.
Sheet G001: The exit access travel distance is stated as 250', however, there is no indication that any of the buildings are sprinklered. Therefore, exit access travel distance would be 200'. Provide clarification and correction in accordance with Table 1017.2.
Sheet G001: The allowable and actual number of stories states that there are two stories. However, none of plans indicate two stories is present on any of the building. Provide clarification or provide the missing floor plans.
Sheet G002: The occupant load calculations provided on the life safety plan is incorrect. Provide a corrected occupant load calculation in accordance with Table 1004.5.
Sheet G002: No egress illumination provided on the egress plan. Provide the location of all egress illumination on the egress plans in accordance with Section 1008.
Sheet G002: Provide clarification as to why buildings #1 and #2 are considered separate buildings and not one. Is this one building with separated occupancies in accordance with Section 508? Additional clarification required. If two buildings are desired; then a fire wall complying with Section 706 would be required.

Provide detail of the elevators and the codes that they will comply with

Provide a list of separate permits required:
Fire sprinkler underground
Fire sprinkler plans
Fire alarm plans

Questions:
Jennifer Peel-Davis
Jennifer.Peel-Davis@tucsonaz.gov
520-837-7033Fire Plans Examiner
06/21/2022 SSHIELD1 ENGINEERING REVIEW Reqs Change See Zoning comments

Final Status

Task End Date Reviewer's Name Type of Review Description
06/21/2022 VVERA1 OUT TO CUSTOMER Completed