Review Date Reviewer's Name Type of Review Description Status Comments
05/18/2022 VFLORES1 PIMA COUNTY - ADDRESSING PIMA COUNTY - ADDRESSING Completed RESOLVED - PLEASE CONTACT PC ADDRESSING UNIT NUMBER NEEDS TO BE ADDED INTO SYSTEM PRIOR TO ISSUANCE Ph# 520-724-9512, EMAIL:ADDRESSING@PIMA.GOV
05/19/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/23/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1. Designate a branch circuit and panel for the new receptacles, also provide a complete panel schedule and locate the panel on the plan. NEC 408.4.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.