Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T22CM03336
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/18/2022 | VFLORES1 | PIMA COUNTY - ADDRESSING | PIMA COUNTY - ADDRESSING | Completed | RESOLVED - PLEASE CONTACT PC ADDRESSING UNIT NUMBER NEEDS TO BE ADDED INTO SYSTEM PRIOR TO ISSUANCE Ph# 520-724-9512, EMAIL:ADDRESSING@PIMA.GOV |
| 05/19/2022 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/23/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. 1. Designate a branch circuit and panel for the new receptacles, also provide a complete panel schedule and locate the panel on the plan. NEC 408.4. Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/23/2022 | NGARCIA3 | OUT TO CUSTOMER | Completed |