Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T22CM03250
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/10/2022 | WBERGER1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 05/10/2022 | WBERGER1 | ENGINEERING | REVIEW | Passed | |
| 05/10/2022 | WBERGER1 | ZONING | REVIEW | Approved | |
| 05/11/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T22CM03250 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Approved BUILDING REVIEW COMMENTS: Denied 1. Sheet G1.2: Provide the rest of the egress path for the 4th and 6th floors. It appears the egress path the leaves the office space does not enter an protected exit. 2. Sheet G1.2: Provide the location of exit signage on the egress plan. MECHANICAL REVIEW COMMENTS: Approved ELECTRICAL REVIEW COMMENTS Approved PLUMBING REVIEW COMMENTS: Approved If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
| 05/13/2022 | JVINCEN1 | FIRE | REVIEW | Approved | |
| 05/24/2022 | ROBERT SHERRY | WATER | REVIEW | Completed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/25/2022 | NGARCIA3 | OUT TO CUSTOMER | Completed |