Review Date Reviewer's Name Type of Review Description Status Comments
06/22/2022 RPARSON1 OIP REVIEW Completed
07/05/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM03230

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Approved

MECHANICAL REVIEW COMMENTS:
N/A

ELECTRICAL REVIEW COMMENTS
Denied
Max OCPD allowed on a 200A buss with a 200A main breaker is 40 A
Plans call for a 50A to be installed
MAX AVAILABLE BACKFEED FOR SES BUS SIZE: 200A BUS x 1.2 = 240A - 200A BREAKER = 40A BACKFEED AVAILABLE
MAX BACKFED CURRENT FOR OCPD: 1.21A(32) x 1.25 = 48.4A TOTAL
The sum of the main and backfeed breakers not exceeding 120% of the busbar
rating NEC 690.64 & 705.12 (D)