| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/22/2022 | RPARSON1 | OIP | REVIEW | Completed | |
| 07/05/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T22CM03230 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Approved BUILDING REVIEW COMMENTS: Approved MECHANICAL REVIEW COMMENTS: N/A ELECTRICAL REVIEW COMMENTS Denied Max OCPD allowed on a 200A buss with a 200A main breaker is 40 A Plans call for a 50A to be installed MAX AVAILABLE BACKFEED FOR SES BUS SIZE: 200A BUS x 1.2 = 240A - 200A BREAKER = 40A BACKFEED AVAILABLE MAX BACKFED CURRENT FOR OCPD: 1.21A(32) x 1.25 = 48.4A TOTAL The sum of the main and backfeed breakers not exceeding 120% of the busbar rating NEC 690.64 & 705.12 (D) PLUMBING REVIEW COMMENTS: N/A If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/05/2022 | VVERA1 | OUT TO CUSTOMER | Completed |