Permit Number: T22CM03219
Parcel: 115200830

Review Status: Active

Review Details: RESUBMITTAL

Permit Number - T22CM03219
Review Name: RESUBMITTAL
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
10/15/2022 ANY BUILDING-RESIDENTIAL REVIEW Active
10/19/2022 PAUL CAMARENA ZONING REVIEW Reqs Change FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: T22CM03219
Carport and Storage Addition (3rd Review)
1914 W RIVERVIEW ST Zoning R-1

TRANSMITTAL DATE:?October 19, 2022


COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1.COMMENT: The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure’s wall facing each interior property line (Table 6.3-2.A). Based on a wall height of 11’-0” the required perimeter yard setback from the proposed carport and storage structure to the west property line is 7’-4”, the proposed setback is 3’-6”. A Design Development Option (DDO) will need to be processed and approved to reduce the setback. DDO application and requirements can be found at: https://www.tucsonaz.gov/files/pdsd/forms/DDO_for_Setback_and_Height_UDC_8.11.20.pdf. A DDO is a separate submittal from the building plan and shall be submitted at: https://www.tucsonaz.gov/pdsd-filedrop, using the Submission Type “Zoning Administration”. If you have questions about the DDO application or process please contact Mark Castro at Mark.Castro@tucsonaz.gov.

2.COMMENT: Based on a wall height of 7’-0” the required perimeter yard setback from the Ramada structure to the north and west property line is 6’-0”, the proposed setback is 3’-0”. At a minimum, a neighbor’s setback waiver is required to reduce the perimeter yard setback. To secure this waiver the following text shall be provided on the plot plan and be signed and dated by the owner of the property to the north and to the west:
My Name is____________________ and I am the owner of the property located at_______________________. I have reviewed the site plan and I have no objection to structure being located or constructed________ feet from the property line as depicted on the site plan.

Signature: _____________________________

Date: _________________________________

If you are unable to secure the neighbor’s setback waiver a Design Development Option (DDO) will need to be processed and approved to reduce the setback. DDO application and requirements can be found at: https://www.tucsonaz.gov/files/pdsd/forms/DDO_for_Setback_and_Height_UDC_8.11.20.pdf. A DDO is a separate submittal from the building plan and shall be submitted at: https://www.tucsonaz.gov/pdsd-filedrop, using the Submission Type “Zoning Administration”. If you have questions about the DDO application or process please contact Mark Castro at Mark.Castro@tucsonaz.gov.



If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov