| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/20/2022 | PCAMARE1 | OIP | REVIEW | Approved | |
| 06/27/2022 | DBENOIT1 | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T22CM03204 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Denied 1. Plans do not include wind uplift calculations. 2018 IRC - 301.1. Provide wind uplift calculations used and verify fastener type and location. 2. Plans do not include deadload calculations. 2018 IRC - 301.1. Provide structural calculations showing the existing roof system is capable of supporting the additional dead loads of the PV system. BUILDING REVIEW COMMENTS: Conditionally Approved 1. Insufficient access pathway at ridge. 2018 IFC - 104.2.1.2. PV system exceeds 33% of roof area and a 3' access is required from the ridge, on each side of the ridge MECHANICAL REVIEW COMMENTS: N/A ELECTRICAL REVIEW COMMENTS Approved PLUMBING REVIEW COMMENTS: N/A If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |