Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Permit Number - T22CM03171
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/28/2022 | PAUL CAMARENA | ZONING | REVIEW | Approved | |
| 04/28/2022 | WBERGER1 | ENGINEERING | REVIEW | Passed | |
| 04/28/2022 | WBERGER1 | NPPO | REVIEW | Passed | |
| 05/10/2022 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | Consolidate pages of construction plans into a single .PDF file as prescribed at the PDSD web site. Roof projections extending into the 3-foot fire separation distance require not less than one-hour fire-resistive construction on the underside, R302.1 (City of Tucson Amended). Update detail C1 on sheet S1.1. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38 or R-30 when extended over the wall top plate for additions under 500 SF. Also, the 2"vent hole is not required. Update detail C1 on sheet S1.1. Smoke alarms are required outside each separate sleeping area, R314.3.2. Show a smoke alarm in each bedroom and outside in the immediate vicinity. Interior alterations require the installation of smoke alarms at existing bedrooms, R314.2.2. Provide notation if the smoke alarms are existing or proposed. |