Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T22CM03150
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/05/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Comment not addressed. [Second comment: Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.] [Initial comment: Provide plans that clearly show what you intend to do and do not have previous approval stamps from 12 years ago. Reference: Section 107.2.1, IBC 2018.] 2. Comment not addressed. [Second comment: Comment not addressed.] [Initial comment: Provide cleanouts for the building sewer that are not located more than 100-feet apart, measured along the developed pipe length from the upstream entrance of the cleanout (i.e. the distance from the cleanout rim to the sewer invert plus the horizontal pipe length shall be less than 100-feet). Reference: Section 708.1.1, IPC 2018.] |