Permit Number: T22CM03150
Parcel: 11450004K

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM03150
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/14/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. [Initial comment: Provide plans that clearly show what you intend to do and do not have previous approval stamps from 12 years ago. Reference: Section 107.2.1, IBC 2018.]
2. Comment not addressed. [Initial comment: Provide cleanouts for the building sewer that are not located more than 100-feet apart, measured along the developed pipe length from the upstream entrance of the cleanout (i.e. the distance from the cleanout rim to the sewer invert plus the horizontal pipe length shall be less than 100-feet). Reference: Section 708.1.1, IPC 2018.]