Permit Number: T22CM03142
Parcel: 134243400

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM03142
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/20/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM03142

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. Uplift calculation not provided. 2018 IRC section R301.1. Provide the calculation used to determine the uplift and fastener capacity. The plans indicate total uplift and fastener pull-out strength but do not indicate how these values were determined.


BUILDING REVIEW COMMENTS:
Approved

MECHANICAL REVIEW COMMENTS:
N/A

ELECTRICAL REVIEW COMMENTS
Denied
1. Missing calculation for Voc adjusted for lowest temperature (16 degree F). 2017 NEC - 690.7. Provide calculation used to determine adjusted maximum voltage based on lowest ambient temperature (not to exceed 600v).


PLUMBING REVIEW COMMENTS:
N/A

If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
06/21/2022 ARUIZ1 OIP REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
06/21/2022 NGARCIA3 OUT TO CUSTOMER Completed