Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T22CM03142
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/20/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T22CM03142 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Denied 1. Uplift calculation not provided. 2018 IRC section R301.1. Provide the calculation used to determine the uplift and fastener capacity. The plans indicate total uplift and fastener pull-out strength but do not indicate how these values were determined. BUILDING REVIEW COMMENTS: Approved MECHANICAL REVIEW COMMENTS: N/A ELECTRICAL REVIEW COMMENTS Denied 1. Missing calculation for Voc adjusted for lowest temperature (16 degree F). 2017 NEC - 690.7. Provide calculation used to determine adjusted maximum voltage based on lowest ambient temperature (not to exceed 600v). PLUMBING REVIEW COMMENTS: N/A If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
| 06/21/2022 | ARUIZ1 | OIP | REVIEW | Completed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/21/2022 | NGARCIA3 | OUT TO CUSTOMER | Completed |