06/16/2022 IMONSHI1 OIP REVIEW Reqs Change FROM: Iman Monshizadeh

PDSD Zoning Review Section

PROJECT: T22CM03133 / Solar

Plot Plan Review (1st Review)

4160 E Montecito / R-1 Zone

TRANSMITTAL DATE: 06/18/2022



Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.



1.COMMENT: After comparing the aerials to the plot plan it has come to my attention that there is a possible non-permitted addition in 2012-2013 on the southern section of the house that the panels are proposed on. In order to place the solar panel on this addition, a permit is required, or panels will have to be moved to a section of the house without unpermitted work.



For questions regarding Zoning comments, please contact me at: Iman.Monshizadeh@tucsonaz.gov

To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp
06/22/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM03133

GENERAL:
Provide written responses to all review comments.30
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
Provide a lag-bolt connection up-lift calculation demonstrating the wind load supporting capability, R301.1. Show the size and total number and spacing of lag bolts.
Provide sufficient standoffs for achieving a point load calculation under 45 pounds, R301.1.


BUILDING REVIEW COMMENTS:
Denied
Provide a lag-bolt connection up-lift calculation demonstrating the wind load supporting capability, R301.1. Show the size and total number and spacing of lag bolts.
Provide sufficient standoffs for achieving a point load calculation under 45 pounds, R301.1.


MECHANICAL REVIEW COMMENTS:
N/A

ELECTRICAL REVIEW COMMENTS
Approved

PLUMBING REVIEW COMMENTS:
N/A

If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
06/22/2022 NGARCIA3 OUT TO CUSTOMER Completed