Permit Number: T22CM03110
Parcel: 133048320

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM03110
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/16/2022 IMONSHI1 OIP REVIEW Approved
06/21/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Needs Review Activity Number: T22CM03110

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. Plans do not indicate existing roof is capable of supporting new loads. 2018 IRC - R301.1. Provide revised plans or structural calculations showing the existing roof is capable of supporting the new dead loads.


BUILDING REVIEW COMMENTS:
Approved

MECHANICAL REVIEW COMMENTS:
N/A

ELECTRICAL REVIEW COMMENTS
Approved

PLUMBING REVIEW COMMENTS:
N/A

If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
06/21/2022 VVERA1 OUT TO CUSTOMER Completed