Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T22CM03081
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/16/2022 | IMONSHI1 | OIP | REVIEW | Approved | |
| 06/22/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T22CM03081 GENERAL: Provide written responses to all review comments.30 Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Denied Provide a lag-bolt connection up-lift calculation demonstrating the wind load supporting capability, R301.1. Show the size and total number and spacing of lag bolts. Provide sufficient standoffs for achieving a point load calculation under 45 pounds, R301.1. BUILDING REVIEW COMMENTS: Denied Provide a lag-bolt connection up-lift calculation demonstrating the wind load supporting capability, R301.1. Show the size and total number and spacing of lag bolts. Provide sufficient standoffs for achieving a point load calculation under 45 pounds, R301.1. MECHANICAL REVIEW COMMENTS: N/A ELECTRICAL REVIEW COMMENTS Approved PLUMBING REVIEW COMMENTS: N/A If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/22/2022 | NGARCIA3 | OUT TO CUSTOMER | Completed |