Permit Number: T22CM03080
Parcel: 116140660

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM03080
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/27/2022 STEVE SHIELDS ZONING REVIEW Approved
04/27/2022 SSHIELD1 ENGINEERING REVIEW Passed
04/27/2022 SSHIELD1 NPPO REVIEW Passed
05/19/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM03080


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Conditionally Approved
1. Fire blocking shall be installed in all walls and concealed spaces including the existing truss roof in areas where the framing is exposed during construction. 2018 IRC R302.11.


BUILDING REVIEW COMMENTS:
Conditionally Approved
1. The window and door note sheet A2 indicates the 2012 IRC, all work shall comply with the 2018 IRC as adopted by the City of Tucson.


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
1. All ducts, air handlers and filter boxes shall be sealed. 2018 IRC M1601.4.1.


ELECTRICAL REVIEW COMMENTS
Denied
1. Update the Electrical notes sheet E1 to indicate a minimum of 90% of all lighting fixtures in the dwelling will contain high-efficacy lamps. 2018 IECC R404.1.
2. Update the Electrical note on sheet E1 to indicate tamperproof outlets will be installed per the 2018 IRC or 2017 NEC 210.52 not the 2012 IRC.
3. The panel schedule for the new sub panel B indicates that the new bath circuit 7 shall be Arc fault protected. Update the schedule to indicate this will be GFCI protected instead.
4. Indicate the location of the smoke detectors in the existing house and the new guest bedroom on the plans. Smoke detectors shall be installed in each sleeping room, outside of each sleeping room in the immediate vicinity of the bedroom. 2018 IRC R314.2.
5. Note on the drawings that all smoke detectors shall receive their primary power from the building wiring with a battery backup and shall be interconnected so that the actuation of one alarm will activate all. 2018 IRC R314.4.
6. Indicate the location of carbon monoxide detectors in the existing house and in the new guest bedroom. Carbon monoxide detectors shall be installed outside of each sleeping area in the immediate vicinity of the bedrooms. 2018 IRC R315.3.
7. Note on the drawings that carbon monoxide devices shall receive their primary power from the building wiring with a battery backup and shall be interconnected so that the actuation of one alarm will activate all. 2018 IRC R314.4. Smoke detectors and carbon monoxide alarms may be combined.


PLUMBING REVIEW COMMENTS:
Conditionally Approved
1. All plumbing fixtures will be low flow type. Toilets are to be 1.6 gallons per flush or less, and showerheads and faucets are to not exceed 2.5 gallons a minute. This will be verified in the field on inspection. Ordinance 7178.
2. All plumbing drain, waste and vent systems shall be tested for leaks in accordance with the 2018 IRC P2503.5 prior to concealing.
3. All hot water lines will be insulated to a minimum of R3 2018 IRC N1103.4.


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov