Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T22CM03063
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/26/2022 | GPENNIN1 | ZONING | REVIEW | Approved | |
04/26/2022 | GPENNIN1 | ENGINEERING | REVIEW | Passed | |
05/07/2022 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A-001; Project Information: This project includes the addition of 1394 SF in an existing building to the existing 2451 SF of the original office. On this sheet, provide the information for the combination of the additional office to the original office, including the combination of the two SF and the two occupant loads. The new C of O will be for the combination of the spaces. 2. Sheet A-001; Project Information: Provide new plumbing fixture calculations for the combined spaces, including water closets, lavatories, drinking fountain, and service sink. 3. Sheet A-103; Symbol Legend: A Wall Symbol for a 3 5/8" steel stud to the roof deck (one hour fire resistance rating) references Details 15 and 16 on Sheet A-701. Those details were not located on that sheet. Please verify. 4. Sheet A-103; Symbol Legend: A Wall Symbol for a new 6" metal stud wall with 5/8" gypsum board on both sides does not provide a reference for that wall detail. Please provide. 5. Sheet A-701; Detail 9: Please provide the low wall metal wall stud size, gauge, and spacing. 6. General: Please provide written responses to all review comments. |
05/10/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Clarify how the design of the med gas room complies with the requirements of Section 503.6, IFC 2018 with respect to protection of openings in the fire barrier (e.g. the 6" exhaust duct), the location of the lower exterior vent and the lack of an upper exterior vent. Reference: Section 5306.2.1, IFC 2018. 2. The door to the med gas room shall be a self-closing, smoke- and draft-control assembly with a minimum fire resistance rating of 1-hour. Reference: Section 5306.2.1, IFC 2018. |
05/10/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Clarify the equipment room elevation and the backflow system detail on sheet P1.3 with regard to supplying water to the dental chairs. Will the chairs be solely provided with bottled water (i.e. show how the water connections to each of the dental chairs are protected from backflow and cross-connection). Reference: Section 608.3, IPC 2018. |
05/10/2022 | ROBERT SHERRY | WATER | REVIEW | Completed | |
05/18/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
05/24/2022 | JPEELDA1 | FIRE | REVIEW | Reqs Change | Plans shall show a combined occupant load List and quantity of med gas shall be provided Ventilation for inside med gas room shall be provided Thank you, Jennifer Peel-Davis Jennifer.Peel-Davis@Tucsonaz.gov 520-837-7033 Fire Plans Examiner |
06/22/2022 | ARUIZ1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |