Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T22CM03063
Parcel: 13355230A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM03063
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/26/2022 GPENNIN1 ZONING REVIEW Approved
04/26/2022 GPENNIN1 ENGINEERING REVIEW Passed
05/07/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A-001; Project Information: This project includes the addition of 1394 SF in an existing building to the existing 2451 SF of the original office. On this sheet, provide the information for the combination of the additional office to the original office, including the combination of the two SF and the two occupant loads. The new C of O will be for the combination of the spaces.
2. Sheet A-001; Project Information: Provide new plumbing fixture calculations for the combined spaces, including water closets, lavatories, drinking fountain, and service sink.
3. Sheet A-103; Symbol Legend: A Wall Symbol for a 3 5/8" steel stud to the roof deck (one hour fire resistance rating) references Details 15 and 16 on Sheet A-701. Those details were not located on that sheet. Please verify.
4. Sheet A-103; Symbol Legend: A Wall Symbol for a new 6" metal stud wall with 5/8" gypsum board on both sides does not provide a reference for that wall detail. Please provide.
5. Sheet A-701; Detail 9: Please provide the low wall metal wall stud size, gauge, and spacing.
6. General: Please provide written responses to all review comments.
05/10/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Clarify how the design of the med gas room complies with the requirements of Section 503.6, IFC 2018 with respect to protection of openings in the fire barrier (e.g. the 6" exhaust duct), the location of the lower exterior vent and the lack of an upper exterior vent. Reference: Section 5306.2.1, IFC 2018.
2. The door to the med gas room shall be a self-closing, smoke- and draft-control assembly with a minimum fire resistance rating of 1-hour. Reference: Section 5306.2.1, IFC 2018.
05/10/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Clarify the equipment room elevation and the backflow system detail on sheet P1.3 with regard to supplying water to the dental chairs. Will the chairs be solely provided with bottled water (i.e. show how the water connections to each of the dental chairs are protected from backflow and cross-connection). Reference: Section 608.3, IPC 2018.
05/10/2022 ROBERT SHERRY WATER REVIEW Completed
05/18/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
05/24/2022 JPEELDA1 FIRE REVIEW Reqs Change Plans shall show a combined occupant load
List and quantity of med gas shall be provided
Ventilation for inside med gas room shall be provided

Thank you,
Jennifer Peel-Davis
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033
Fire Plans Examiner
06/22/2022 ARUIZ1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review