Permit Number: T22CM03014
Parcel: 137330490

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM03014
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/15/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM03014


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Denied
Show the sum of the main and backfeed breakers not exceeding 120% of the busbar rating, NEC 690.64 & 705.12(D).


MECHANICAL REVIEW COMMENTS:
N/A


ELECTRICAL REVIEW COMMENTS
Denied
Show the sum of the main and backfeed breakers not exceeding 120% of the busbar rating, NEC 690.64 & 705.12(D).


PLUMBING REVIEW COMMENTS:
N/A


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
06/21/2022 ARUIZ1 OIP REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
06/21/2022 VVERA1 OUT TO CUSTOMER Completed