Review Date Reviewer's Name Type of Review Description Status Comments
06/16/2022 IMONSHI1 OIP REVIEW Approved
06/21/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Approv-Cond Activity Number: T22CM03007

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Conditionally Approved
1. Uplift calculation not provided. 2018 IRC section R301.1. Provide the calculation used to determine the uplift and fastener capacity. The plans indicate total uplift and fastener pull-out strength but do not indicate how these values were determined.


BUILDING REVIEW COMMENTS:
Approved

MECHANICAL REVIEW COMMENTS:
N/A

ELECTRICAL REVIEW COMMENTS
Approved

PLUMBING REVIEW COMMENTS:
N/A

If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
06/21/2022 NGARCIA3 OUT TO CUSTOMER Completed