Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T22CM03006
Parcel: 125021190

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM03006
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/16/2022 IMONSHI1 OIP REVIEW Approved
06/21/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Approv-Cond Activity Number: T22CM03006

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Approved

MECHANICAL REVIEW COMMENTS:
N/A

ELECTRICAL REVIEW COMMENTS
Conditionally Approved
1. Missing arc-fault protection information. 2017 NEC - 690.11. Arc-fault protection of PV system is required. Manufacturer's specs of equipment do not clearly indicate this and installer shall ensure this is installed.


PLUMBING REVIEW COMMENTS:
N/A

If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
06/21/2022 NGARCIA3 OUT TO CUSTOMER Completed