Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM02977
Parcel: 11921040C

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T22CM02977
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/26/2022 SAMUEL ROGERS ZONING REVIEW Reqs Change FROM: Samuel Rogers
PDSD Zoning Review Section

PROJECT: T22CM02977 (Project Number)
Construction of 3 baseball fields, new restroom, walking paths & associated parking (Project Type) (1st Review)
3700 S MISSION RD (Address)

TRANSMITTAL DATE: 04/26/2022

DUE DATE: 05/17/2022

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


01. COMMENT: DP22-0110 must be issued prior to the issuance of this building permit. Once the DP is approved this building permit will be reviewed for compliance with the DP. More comments may be forthcoming.


If you have any questions about this transmittal, Contact Samuel Rogers at Samuel.Rogers@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans
04/28/2022 JVINCEN1 FIRE REVIEW Approved
05/02/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet s1.0; General Structural Notes (Foundations): Note 1 indicates a geotechnical report was used for the foundation design. Please provide that report.
2. Sheet a1.0: Please provide a code analysis for the Restroom Building and the Concession Building. Include Occupancy Classification, Building SF, Construction Type, and Occupant Load.
3. Sheet a1.0; Reference Floor Plan: Please add a note in the Exterior Seating Area to follow the requirements of the IBC Section 1109.11 for accessible seating and standing spaces.
4. General: Please provide a project valuation (labor + materials).
5. General: Please provide a Special Inspections Certificate with Parts A and B completed. This form may be found at www.tucsonaz.gov/PDSD.
6. General: Please provide written responses to all review comments.
05/04/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The maximum distance between cleanouts for the building sewer shall be 100-feet, measured along the developed pipe length from the opening of the cleanout to the next cleanout access point. Reference: Section 708.1.1, IPC 2018.
05/04/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
05/04/2022 ROBERT SHERRY WATER REVIEW Completed
05/16/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
05/31/2022 SSHIELD1 ENGINEERING REVIEW Needs Review
05/31/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/31/2022 VVERA1 OUT TO CUSTOMER Completed