06/23/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T22CM02966
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

The City of Tucson adopted the 2018 IRC with amendments on 1/1/2019. Show the current code reference on the plans.

A living space with cooking features (An ADU) is an independently functioning dwelling and requires compliance with the 2018 IRC and City of Tucson building ordinances for Family Dwelling requirements.

Each dwelling unit with kitchen requires a separate Pima County assigned street address, R319. Notate each dwelling address on the site plan (or remove cooking appliances).

A new dwelling unit requires collection of development impact fee when the building permit is processed, City of Tucson Ordinance #11203.

GENERAL COMMENTS (for dwelling with kitchen):

1. A dwelling unit (living space with kitchen) providing complete independent living facilities requires compliance with design ordinances for handicap, solar water, photo-voltaic, gray water and EV charging preparations. Design Ordinances adopted by the City of Tucson.
2. Show compliance with the Inclusive Home Design Ordinance adopted by the City of Tucson Ordinance #10463 on 10/16/2007. Notate accessible route, minimum door width, changes in floor elevation, door hardware, electrical outlet reach range, grab bar reinforcement, etc.
3. All SFR and Duplex plans submitted after March 1, 2009 require a solar water system, or future installation preparation City of Tucson Ordinance #10549 with one of the following provisions: ½”control conduit and two ¾” copper piping for water with rooftop termination; straight 3” capped sleeve; or an accessible attic (clear path 30” wide x 30” high) over the water heater. Show appropriate notation.
4. All SFR and Duplex plans submitted after July 1, 2009 require a solar photo-voltaic system, or future installation preparation City of Tucson Ordinance #10549 .
a. Show a minimum 300 SF clear solar-ready zone on a roof or framing plan, T103.3. Model plans should show four typical south facing roof surfaces.
b. Label a double breaker space for future Photo Voltaic on the panel schedule opposite end from the main/supply side, T103.9. Update breaker space location.
5. All construction drawings submitted after June 1, 2010 for one- or two-family dwellings must provide gray water utilization or preparation, Ordinance #10579/11089 revised July 9, 2013. The ordinance revision now requires a gray drain line discharge from one fixture for a one story dwelling. Additional gray fixture drains are optional. Show a second clothes washer standpipe plumbed to an exterior wall above grade when feasible, or a bathing fixture drain looped 3’ beyond an exterior wall below grade before connection to the building drain. See details at https://www.tucsonaz.gov/pdsd/water-energy-conservation
6. Show compliance with the Electric Vehicle Supply Equipment Ordinance adopted by the City of Tucson Ordinance #11844 on 6/22/2021. Include a 40 ampere 240 volt dedicated branch circuit with a NEMA 14-50R receptacle for charging an electric vehicle at a proposed parking space or show the distance from transit or a bike boulevard as not greater than a quarter-mile.

SITE PLAN:

1. Identify each dwelling with a Pima County issued addresses.
2. Update the electric and water lines from meter to building, R106.1.1. Show all utility point of connections without dependance on another dwelling. Consider a single multi-meter location on the property.

PLANS:

1. Show a maximum ½” floor elevation changes at a notated accessible route entrance on the floor plan, R106.1.1.
2. Provide a complete Roof Framing Plan with size for a ridge beam or an interior load bearing wall with foundation, R106.1.

SECTIONS - DETAILS:

1. Show one-hour fire-resistive framed construction separating dwellings in compliance with IBC Table 721.1(2). Show the one-hour wall location and detail the assembily.
2. Show a complete cross-section detail of the new exterior wall, R106.1.1. Show the minimum 12” reinforced footing depth below the undisturbed ground surface R403.1. Show exterior wood siding, sheathing and wall framing with a 6” clearance above the ground, R317.1 item 5. Update the details on sheet S-04.
3. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38.

PLUMBING PLANS:

1. Tucson Water Department limits flow rates for each water meter size in compliance with P2903.7. Show an appropriate yard pipe bypassing the existing dwelling and the water meter size.
2. Show the kitchen sink on the waste isometric sheet S-06.

MECHANICAL PLANS:

1. Provide (an HVAC system with fresh air intake) whole-house mechanical ventilation, or controlled exhaust with a calculated airflow rate, R303.4; N1103.6 & M1505.4. Show the system and appropriate flow rate setting on the plans. A two or three bedroom dwelling under 1501 SF requires a 45 CFM continuous setting.
2. Provide demand calculations in accordance with Manual J/S/D standards, M1401.3, M1601.1. Systems shall be sized in accordance with Manual S based on building loads calculated in accordance with Manual J and duct systems sized in accordance with Manual D. Notate if the mechanical plans if system calculations will be provided by deferred submittal.
3. Update the code reference at note #4 sheet S-07.

ELECTRICAL PLANS:

1. Provide a panelboard clear working space of 30” wide x 36” deep, E3405.2.
2. Provide a panel schedule showing all appliances. If stove and water heater operate with gas include a gas piping schedule on the plumbing plan.
3. Show a 2O AMP small appliance circuit at the kitchen countertop receptacle outlet between the sink and refrigerator, E3703.2 and E3901.3. GFCI protected, E3902.6.
4. Protection of all interior 15A & 20A circuits serving outlet locations (except garage, kitchen, and bathrooms) including receptacles, lights and smoke detectors requires combination type arc-fault circuit interrupters, E3902.16.
5. Show a wall switch controlled exterior light at entrances or exits, E3903.3.
6. TEP may require the service panel for the property at the closest building to the service transformer. A service line change or a new meter location must be coordinated with TEP for approval. Show an underground feeder from a dual meter to the more distant dwelling.
7. Provide a Riser Diagram showing all dwellings and feeder sizes, NEC 225.30 and E3403. Show a Riser Diagram providing service disconnect of either dwelling without service disruption of another dwelling.
8. Provide the Electric Vehicle Supply Equipment 40 ampere 240 volt dedicated branch circuit with a NEMA 14-50R receptacle and label the circuit “EV Ready” and locate the receptacle at a parking area, N1104.2.1. Include the Electric Vehicle load entry (typically 7680 watts) in the electrical load calculations (continuous demand) like the HVAC entry, N1104.2.2.

OUTDOOR LIGHTING CODE

1. Show the proposed fixture as full cut-off FCO style or provide an Outdoor Lighting Calculation including all exterior fixtures on the property for determining exterior lighting limits.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Energy Certificate: (Mandatory) place near the indoor furnace or in utility room, N1101.14. Add notation to plans.

Please contact the plans reviewer if you have any questions:
Ken Van Karsen
(520) 837-4912 PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review
06/23/2022 CVASQUE2 PIMA COUNTY - ADDRESSING PIMA COUNTY - ADDRESSING Reqs Change Pending zoning approval, 2 separate addresses required at issuance for the project. Contact Pima County Addressing at addressing@pima.gov or (520)724-9512 to obtain addresses.
06/30/2022 PCAMARE1 ENGINEERING REVIEW Reqs Change This comment is still applicable, After reviewing the Letter of Map Amendment determination document the outcome of this letter is the structure is removed from the SFHA. "PORTIONS OF THE PROPERTY REMAIN IN THE SFHA". With that being said the proposed ADU would require a Floodplain permit.

This project is within a mapped flood hazard area and requires a Floodplain Use Permit (FUP.)
Please start a new FUP at our permit application web page: https://docs.tucsonaz.gov/Forms/tucsonpermitapp.
Instructions:
Is this for a new or existing activity application? – Please select New Application.

Submission Type – Select Floodplain Use Permit.

Project Name – Enter a name for your project.

Select Street Name from the list. You can type the first two letters or number to get closer to your choice in the list. Then select the rest of the address in the boxes provided.

Type of Permit – Select Commercial or Residential (Residential is for work on single family residences and duplexes.)

Complete the Applicant Info.
Complete the Contractor, Owner and Architect/Engineer sections as applicable.

Supporting Documentation Upload – Provide a complete cost estimate for the project. You may also provide additional documents you think will be helpful.

Sign the application and submit.

You will be given an activity number for your submittal. Please copy and send this number back to us so we can continue the review.
07/08/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T22CM02966
938 E 8th St - R-2
New ADU (2nd Review)

TRANSMITTAL: July 8, 2022

This was not addressed. Provided a detail comment response letter with your submittal that clearly shows how you have addressed all comments with your next submittal.

This site is located in the R-2 zone (UDC 4.7.9). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.6, .9, & .10.

1. The lot coverage is still not correct. Based on a lot size of 50’ x 150’ the total lot square footage is 7,500 sq. ft. The plans show a total of building sq. ft. & parking of 2,675.38 sq. ft. for a lot coverage of 35.7%. The lot coverage calculation is not correct and should include all vehicular use areas, measured within the outside edges of any area allocated to vehicle use, whether improved or unimproved. See UDC Article 6.4.3.B.3.b.

2. The parcel dimensions show on the plan are not correct. Per the Rieckers Addition final plat recorded in Book 3 Page 127 the lot size is 50’ x 150’. Provide parcel dimensions on the plot plan

3. This comment was not addressed correctly. Based on Paving plan I-400 found at: https://www.tucsonaz.gov/apps/maps-and-records/construction-plans/details/I-400, the distance from centerline of 8th to curb is 19.6’ and from curb to property line is 20’. Provide a dimension from the centerline of 8th St to the face of curb and from the face of curb to the north property line.

4. This comment was not addressed correctly. Based on Paving plan I-836 found at: https://www.tucsonaz.gov/apps/maps-and-records/construction-plans/details/I-836, the distance from centerline of Caddie to the property line is 21.5’. Provide a dimension from the centerline of Caddie St to the south property line.

5. This comment was not fully addressed. Show all utilities on the plot plan.

6. This comment was not fully addressed. Provide the legal description on the plot plan.

7. This comment was not fully addressed. As perimeter yard setbacks are based on a measurement from design grade to the highest point of the exterior wall UDC Article 6.4.5.B & Figure 6.4.5-A. Provide fully dimensioned elevations with the next submittal.

8. This comment was not fully addressed. Clearly demonstrate on the plan that the requirements of UDC Articles 6.6.3.B.2 and 6.6.3.B.3 are met.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.