Review Details: 3RD PARTY REVIEW - COMMERCIAL
Permit Number - T22CM02964
Review Name: 3RD PARTY REVIEW - COMMERCIAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/04/2022 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: T22CM02964 & T22CM02967 3231 N Freeway Industrial Lp - I-1 – DP21-0338 Shell Bldg & TI – Commercial Storage & General Merchandise Sales (1st Review) TRANSMITTAL: May 4, 2022 This site is located in the I-1 zone (UDC 4.7.29). The proposed uses are permitted uses in this zone (Table 4.8-5) subject to Use Specific Standards 4.9.10.A & 4.9.13.Q. 1. Zoning has reviewed the building plans for compliance with DP21-0338 and although it appears that the plans match Zoning cannot approve the building plans until the DP is approved by all review agencies. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. |
| 05/04/2022 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed | |
| 05/11/2022 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Correct the conversion from water fixture units to demand in both water calculations (TI and Shell). Reference: Section 107.2.1, IBC 2018. |
| 05/24/2022 | JPEELDA1 | FIRE | REVIEW | Reqs Change | Per the DP the building was to have fire sprinklers installed. Plans shall show that the building shall have fire sprinklers installed per NFPA 13 and the plans submitted to TFD for a permit. Building will also require a dedicated function fire alarm system per NFPA 72 and the plans submitted to TFD for a permit. Questions: Jennifer Peel-Davis Jennifer.Peel-Davis@tucsonaz.gov 520-837-7033Fire Plans Examiner |
| 05/26/2022 | WILDAN | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | Completed | |
| 05/26/2022 | DBENOIT1 | 3RD PARTY REVIEW-COMMERCIAL | AT 3RD PARTY OFFICE | Completed | |
| 06/21/2022 | SSHIELD1 | ENGINEERING | REVIEW | Reqs Change | See Zoning comments |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/22/2022 | NGARCIA3 | OUT TO CUSTOMER | Completed |