Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T22CM02962
Parcel: 141177120

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM02962
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/29/2022 JVINCEN1 FIRE REVIEW Approved
05/05/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM02962

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. The Geotechnical Report submitted is dated March 09, 2004 and references International Building Code 2000. Submit revised report based on IBC 2018 since Arizona have adopted the International Building Code 2018.
2. The Structural Calculations submitted for Jamb Stud Design DJM1 shows excessive deflections on page 90. Revise the size and resubmit calculations.
3. The Structural Calculations submitted for Jamb Stud Design DJM2 shows excessive deflections on page 96. Revise the size and resubmit calculations.
4. The Structural Calculations submitted for Jamb Stud Design DJM3 shows excessive deflections on page 102. Revise the size and resubmit calculations.
5. The Structural Calculations submitted for Jamb Stud Design DJM4 shows excessive deflections on page 108. Revise the size and resubmit calculations.
6. The Structural Calculations submitted for Jamb Stud Design DJM5 shows excessive deflections on page 114. Revise the size and resubmit calculations.
Submit a response letter addressing these correction items and provide bubbles on the revisions to the drawings.


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Approved
1. Approved for core and shell. Will have to provide plans for tenant buildout


ELECTRICAL REVIEW COMMENTS
Approved

PLUMBING REVIEW COMMENTS:
Denied
First Plumbing Review: Shell only
1). Plan set needs to be accompanied by site utility piping plan for continuation of sewer, fire main. -IPC 106.3.1
2). Roof Plan A2.1 primary scuppers need secondary drains illustrated along with sizing calculations for both/. -IPC 1108
3). If scuppers on plan page A2.1 have downspouts they will need to be illustrated along with sizing calculations. -IPC 1106.3


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
05/06/2022 SAMUEL ROGERS ZONING REVIEW Approved FROM: Samuel Rogers
PDSD Zoning Review Section

PROJECT: T22CM02962 (Project Number)
Shell Building (Project Type) (1st Review)
7375 S HOUGHTON RD (Address)

TRANSMITTAL DATE: 04/26/2022

DUE DATE: 05/17/2022

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


01. COMMENT: Any new structures on a commercial lot are required to be shown on a Development Package (DP) prior to the issuance of any building permits. Once the DP is issued Zoning will be able to review the building plan against it.


If you have any questions about this transmittal, Contact Samuel Rogers at Samuel.Rogers@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans
05/11/2022 ROBERT SHERRY WATER REVIEW Completed
07/22/2022 SBLOOD1 ENGINEERING REVIEW Approved
08/01/2022 EHAMBLI1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
08/02/2022 VVERA1 OUT TO CUSTOMER Completed