Permit Number: T22CM02925
Parcel: 125075880

Address:
301 N OLSEN AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM02925
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/09/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T22CM02925
301 N Olsen Ave - R-1
Attached Garage & Play Room (2nd Review)

TRANSMITTAL: June 9, 2022

This site is located in the R-1 zone (UDC 4.7.8). A single-family residence is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.5 – 9.

COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure’s wall facing each interior property line (Table 6.3-2.A).
1. Based on a wall height of 17’-6” the required perimeter yard setback from the proposed addition to the west property line is 11’-8”, proposed setback is 9’-6”.

The minimum setback to the front street perimeter property line is the greater of twenty (20) feet, or one and one-half (1 ½) the height of the proposed wall ((UDC 6.4.5.C.1.a).
2. Based on a wall height of 17’-6” the required front street perimeter yard setback is 26’-3”, proposed setback is 19’-0”.

A Design Development Option (DDO) must be submitted and approved to reduce the required setback,
DDO application and requirements can be found at: https://www.tucsonaz.gov/files/pdsd/forms/DDO_for_Setback_and_Height_UDC_8.11.20.pdf. A DDO is a separate submittal from the building plan and shall be submitted at: https://www.tucsonaz.gov/pdsd-filedrop, using the Submission Type “Zoning Administration”. If you have questions about the DDO application or process please contact Mark Castro at Mark.Castro@tucsonaz.gov.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
06/14/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change Provide a complete revised plan set after Zoning processing.